Scope Of Delivery; Accessories; Description And Function; Description Of The Product - Wilo Stratos GIGA Serie Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Stratos GIGA Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

English
5.3

Scope of delivery

5.4

Accessories

6

Description and function

6.1

Description of the product

10
• Mixtures with a proportion of glycol of > 10% influence the p-v
pump curve and the flow calculation.
NOTE:
The flow value shown on the IR-Monitor display or output to the
building management system must not be used to control the pump.
This value is merely an indicator of general trends.
A flow value is not an output on every type of pump.
NOTE:
Always read and follow the material safety data sheet for the fluid
being pumped!
• Stratos GIGA pump
• Installation and operating instructions
Accessories must be ordered separately:
• Three mounting brackets with fixation elements for installation on a
base
• Installation aid for mechanical seal
• IR-Monitor
• IF-Module PLR for connecting to PLR/interface converter
• IF-Module LON for connection to the LONWORKS network
• BACnet IF-Module
• Modbus IF-Module
• CAN IF-Module
See catalogue for detailed list.
NOTE:
IF-Module may only be plugged in when the pump is deenergized
(voltage-free).
The Wilo-Stratos GIGA high-efficiency pumps are glanded pumps
with built-in power adjustment and "Electronic Commutated Motor"
(ECM) technology. The pumps are designed as single-stage low-
pressure centrifugal pumps with flange connection and mechanical
seal.
The pumps can be installed both directly as pipe installation pumps in
sufficiently secured pipes or be placed on a foundation base.
The pump housing is designed as an in-line construction; i.e. the suc-
tion and pressure-side flanges are on one axis. All pump housings are
provided with a pump base. Installation on a foundation base is
recommended.
WILO SE 01/2014