Install The Air Baffles; Connect The Control Cables - ABB ACQ580-04 Guía De Instalación Rápida

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 23

Install the air baffles

See figure
W
on page
56
hardware manual.

Connect the control cables

See figure
X
on page 56.
1. Ground the outer shields of all external control cables 360 degrees at the cabinet lead-
through.
2. Ground the pair-cable shields of external control cables to a grounding clamp below
the control unit. Leave the other end of the shields unconnected or ground them
indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V.
3. Connect the conductors to the appropriate terminals of the control unit. See page 14.
4. Wire the optional modules if included in the delivery.
and Guidelines for planning the cabinet installation in the
EN – USA Quick installation guide 13
USA
DA
DE
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
Tabla de contenido
loading

Tabla de contenido