12 EN – R6...R9 Quick installation guide
For information on reforming the capacitors, see Converter module capacitor
reforming instructions (3BFE64059629 [English]), available on the Internet at
www.abb.com/drives/documents.
Select the power cables
R0-
R4
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.
R6-
R9
Ensure the cooling
R6-
R9
See table
I
on page
operating temperature range of the drive is -15 to +50 °C (+5 to +122 °F). No
condensation or frost is allowed. For more information on the ambient temperature
and derating, see chapter Technical data in ACQ580-01 (0.75 to 250 kW) hardware
EN
manual (3AXD50000035866 [English]).
DE
Protect the drive and input power cable
ES
See tables III,
IV
If you use gG fuses, make sure that the operating time of the fuse is below
FR
0.5 seconds. Follow the local regulations.
IT
Install the drive on the wall
RU
Warning! The drive module is heavy (42 to 103 kg / 93 to 227 lb). Use a
SV
suitable lifting device. Do not lift the module manually. Make sure that the wall
and the fixing devices can carry the weight.
See figure
R6...R9 Figures A
9
(UL: table
II
on page 9) for the heat dissipation. The allowed
and
V
on page
10
for the fuses.
on page 83.