4. Installing the refrigerant piping
4.7. Precautions when reusing existing R22 refrigerant pipes
• Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer.
• If the diameter of the existing pipes is different from the specified diameter, refer to technological data materials to confirm if the pipes can be used.
The existing pipe thickness meets specifica-
tions and the pipes are not damaged.
Check if the existing air conditioner can operate.
After operating the cooling system for about 30
minutes, do a pump down work.
Disconnect the existing air conditioner from the
pipes.
Attach the new air conditioner
Perform the airtight test, vacuum air purging,
additional refrigerant charging (if necessary),
and gas leak check.
Test run
* Refer to 7.2.
<Limits of refrigerant piping installation>
<
ZRP71
: A+B+C
50 m
* "D" is for triple.
Fig. 4-8

5. Drainage piping work

Outdoor unit drainage pipe connection
When drain piping is necessary, use the drain socket or the drain pan (option).
ZRP35, 50
Drain socket
PAC-SJ08DS-E
Drain pan
PAC-SG63DP-E
8
Measure the existing pipe thickness and
check for damage.
* If the existing air conditioner cannot operate, use
a refrigerant recovery device to collect the refrigerant.
* In case existing pipes were used for gas or oil
heat pump systems, be sure to clean the pipes
for ZRP100-140 models.
Use new pipes for ZRP35-71 models.
4.8. For twin/triple combination (Fig. 4-8)
• When this unit is used as a FREE COMPO MULTI unit, install the refrigerant pip-
ing with the restrictions indicated in the drawing on the left. In addition, if the restric-
tions are going to be exceeded, or if there are going to be combinations of indoor
and outdoor units, refer to installation instructions for the indoor unit for details
about the installation.
A Indoor unit
B Outdoor unit
C Multi distribution pipe (option)
D Height difference (Indoor unit-
Outdoor unit) Max. 30 m
E Height difference (Indoor unit-
Indoor unit) Max. 1 m
A: Main piping
B, C, D: Branch piping
ZRP60, 71
PAC-SH71DS-E
PAC-SG64DP-E
The existing pipe thickness does not meet
specifications or the pipes are damaged.
The existing pipes cannot be reused.
Use new pipes.
Permissible total
Outdoor unit
piping length
A+B+C+D
ZRP71
50 m and less
Outdoor unit
│B-C│ or │B-D│or │C-D│
ZRP71
8 m and less
A+B or A+C
Charge-less
or
piping length
A+D
A+B+C+D
30 m and less
No. of bends
Within 15