2.4 Electrical connections

Connection to the electrical grid
B
The unit's electrical safety is only guaranteed when correctly connected to an efficient earthing system exe-
cuted according to current safety standards. Have the efficiency and suitability of the earthing system checked
by professionally qualified personnel. The manufacturer is not responsible for any damage caused by failure
to earth the system. Also make sure that the electrical system is adequate for the maximum power absorbed
by the unit, as specified on the boiler dataplate.
The boiler is prewired and provided with a Y-cable and plug for connection to the electricity line. The connections to the
grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum
opening of at least 3 mm, interposing fuses of max. 3A between the boiler and the line. It is important to respect the
polarities (LINE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green wire) in making connections to the electrical
line. During installation or when changing the power cable, the earth wire must be left 2 cm longer than the others.
B
The user must never change the unit's power cable. If the cable gets damaged, switch off the unit and have it
changed solely by professionally qualified personnel. If changing the electric power cable, use solely "HAR
H05 VV-F" 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.
Room thermostat (optional)
B
CAUTION: The room thermostat must have clean contacts. CONNECTING 230 V. TO THE TERMINALS OF
THE ROOM THERMOSTAT WILL IRREPARABLY DAMAGE THE ELECTRONIC CARD.
When connecting a remote timer control or a timer switch, do not take the power supply for these devices from
their cut-out contacts. Their power supply must be taken with a direct connection from the mains or with bat-
teries, depending on the kind of device.
External probe (optional)
Connect the probe to its respective terminals. The maximum permissible length for the boiler - external probe connec-
tion electrical cable is 50 m. A normal 2-wire cable can be used. The external probe should preferably be installed on
the North, North-West wall or that facing the largest area of living room. The probe must never be exposed to the early
morning sun or, insofar as possible, direct sunlight; protect it if necessary. In any case, the probe must not be installed
near windows, doors, ventilation openings, flues or heat sources that could affect the reading.
68
fig. 25 - External probe positioning not recommended