For installation:
A
Insert the diameter 100 M-F pipe sections with fume inspection "1" and the respective seals "2" from the outside
of the modules for each flue connection.
B
Respect the distance given in the box "B" of fig. 33. This distance must be increased by 5 mm with each addi-
tional module.
C
Open the cabinets and install the anti-backflow valve "3" on eachflue connection D=80mm
D
Make sure to correctly fit the seals.
E
Lengthen the diameter 100mm extensible part of each valve until it rests on the inner part of the casing. Fix
with the screw "4".
F
Pour 1/2 litre of water on each flue in order to fill the respective traps and anti-backflow valves. Repeat the
above steps for all the flue connections of the modules.
EN
fig. 33
fig. 34
cod. 3540H322 - 09/2008 (Rev. 01)
75