Lamborghini Caloreclima Reply 51 Instrucciones De Uso página 82

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Remote
Card
control
20
P20
21
P21
22
P22
23
P23
24
P24
25
P25
26
P26
27
P27
28
P28
P02 (Conf.
29
Menu)
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to
modify the value of a parameter: the change will be automatically saved.The Max. Heating Power parameter can be
modified in Test Mode (refer to relevant section).Press the Reset button to return to the Service Menu. Press the Reset
button for 10 seconds to exit to the card Service Menu.
82
Description of Transparent Parameters
Not used (P02=1)
Hot water tank hysteresis (P02=2)
Hot water tank hysteresis (P02=3)
Not used (P02=4)
Hot water tank hysteresis (P02=5)
Hot water tank hysteresis (P02=6)
Not used (P02=1)
Primary setpoint (P02=2)
Primary setpoint (P02=3)
Not used (P02=4)
Primary setpoint (P02=5)
Primary setpoint (P02=6)
Modulating pump adjustment temperature (P02=1)
Modulating pump adjustment temperature (P02=2)
Modulating pump adjustment temperature (P02=3)
Modulating pump adjustment temperature (P02=4)
Modulating pump adjustment temperature (P02=5)
Modulating pump adjustment temperature (P02=6)
Primary exchanger protection temperature (P02=1)
Primary exchanger protection temperature (P02=2)
Primary exchanger protection temperature (P02=3)
Primary exchanger protection temperature (P02=4)
Primary exchanger protection temperature (P02=5)
Primary exchanger protection temperature (P02=6)
Not used
Not used
Not used (P02=1)
Legionella protection (P02=2)
Legionella protection (P02=3)
Not used (P02=4)
Legionella protection (P02=5)
Legionella protection (P02=6)
Operation selection Variable output relay
Mains Voltage Frequency
Fan max. frequency in DHW (P02=1)
Fan max. frequency in DHW(P02=2)
Fan max. frequency in DHW (P02=3)
Fan max. frequency in DHW (P02=4)
Fan max. frequency in DHW (P02=5)
Fan max. frequency in DHW (P02=6)
cod. 3540H322 - 09/2008 (Rev. 01)
Reply 51 - 71 - 101
Range
Not used
0-100°C
0-100°C
Not used
0-100°C
0-100°C
Not used
0-100°C
0-100°C
Not used
0-100°C
0-100°C
0-30°C
0-30°C
0-30°C
0-60°C
0-60°C
0-60°C
0-30°C
0-30°C
0-30°C
0-60°C
0-60°C
0-60°C
Not modifiable
Not modifiable
Not used
0-7=Activation
days
0-7=Activation
days
Not used
0-7=Activation
days
0-7=Activation
days
0=Burner lit
1=Legionella pump
0=50Hz,1=60Hz
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Do not modify
Default
2°C
2°C
2°C
2°C
80°C
80°C
80°C
80°C
25°C
25°C
25°C
30°C
30°C
30°C
25°C
25°C
25°C
30°C
30°C
30°C
4
8
0=No prot.
0=No prot.
0=No prot.
0=No prot.
0=Burner lit
0=50Hz
185 Hz
185 Hz
185 Hz
215 Hz
215 Hz
215 Hz
EN
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Reply 71Reply 101

Tabla de contenido