Troubleshooting - Lamborghini Caloreclima TAURA D MCS Serie Instrucciones De Uso

Ocultar thumbs Ver también para TAURA D MCS Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

TAURA D MCS
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
3.
The Maximum Heating Power parameter can be modified also in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"In" - Information Menu
6 pieces of information are available.
Press the Heating buttons to scroll the list of information in increasing or decreasing or-
der . Press the DHW buttons to display the value.
Con-
Description
tents
t01
NTC Heating sensor (°C)
t02
NTC Safety sensor (°C)
t03
NTC DHW sensor (°C)
t04
NTC External sensor (°C)
L05
Actual burner power (%)
F06
Actual Flame resistance(Ohm)
Notes:
1.
In case of damaged sensor, the card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu or exiting occurs automatically after 15 minutes.
"Hi" - History Menu
The card can store the last 11 faults: the History datum item H1: represents the most re-
cent fault that occurred; the History datum item H10: represents the least recent fault that
occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Re-
mote Timer Control.
Press the Heating buttons to scroll the list of faults in increasing or decreasing order.
Press the DHW buttons to display the value.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"rE" - History Reset
Press the Eco/Comfort button for 3 seconds to delete all the faults stored in the History
Menu: the card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs
automatically after 15 minutes.
4.2 Startup
Before lighting the boiler
Check the seal of the gas system.
Check correct prefilling of the expansion tank.
Fill the water system and make sure all air contained in the boiler and the system
has been vented.
Make sure there are no water leaks in the system, DHW circuits, connections or boil-
er.
Check correct connection of the electrical system and efficiency of the earthing sys-
tem.
Make sure the gas pressure for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
Checks during operation
Switch the unit on.
Check the tightness of the fuel circuit and water systems.
Check the efficiency of the flue and air/fume ducts while the boiler is working.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water
production stages.
Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.
Make sure that with no demand for heating, the burner lights correctly on opening a
hot water tap. Check that in heating mode, on opening a hot water tap, the heating
circulating pump stops and there is regular production of hot water.
Make sure the parameters are programmed correctly and carry out any required
customisation (compensation curve, power, temperatures, etc.).
Range
between 05 and 125°C
between 05 and 125°C
between 05 and 125°C
between -30 and 70°C (negative values flash)
00%=Min., 100%=Max.
00-99 Ohm (-- = burner off)
cod. 3541A220 - 01/2011 (Rev. 00)
4.3 Maintenance
Periodical check
To ensure correct operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
The control and safety devices (gas valve, flow meter, thermostats, etc.) must func-
tion correctly.
The fume exhaust circuit must be perfectly efficient.
(Sealed chamber boiler: fan, pressure switch, etc. -The sealed chamber must be
tight: seals, cable glands, etc.)
(Open chamber boiler: anti-backflow device, fume thermostat, etc.)
The air-fume end piece and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. For possible cleaning
do not use chemical products or wire brushes.
The electrode must be properly positioned and free of scale.
=
=
fig. 17 - Electrode positioning
The gas and water systems must be airtight.
The water pressure in the cold water system must be about 1 bar; otherwise, bring
it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must correspond to that given in the respective tables.

4.4 Troubleshooting

Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to eliminate
the fault.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
List of faults
Table. 8
Fault
Fault
Possible cause
code
No gas
Ignition/detection electrode fault
A01
No burner ignition
Faulty gas valve
Gas valve wiring disconnected
Ignition power too low
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor damaged
Overtemperature protec-
A03
tion activation
No water circulation in the system Check the circulating pump
Air in the system
F04
Card parameter fault
Wrong card parameter setting
Fume pressure switch fault
Wrong card parameter setting
(contact fails to close)
Wiring disconnected
F05
Fan fault
Faulty fan
Card fault
Low pressure in the gas system
No flame after the ignition
A06
phase
Burner minimum pressure setting Check the pressures
F07
Card parameter fault
Wrong card parameter setting
Wiring disconnected
A09
Gas valve fault
Faulty gas valve
Cure
Check the regular gas flow to the
boiler and that the air has been elimi-
nated from the pipes
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Check the gas valve and replace it if
necessary
Check the wiring
Adjust the ignition power
Check the ionisation electrode wiring
Check the card
Check the correct positioning and
operation of the heating sensor
Vent the system
Check the card parameter and modify
it if necessary
Check the card parameter and modify
it if necessary
Check the wiring
Check the fan
Check the card
Check the gas pressure
Check the card parameter and modify
it if necessary
Check the wiring
Check the gas valve and replace it if
necessary
EN
27
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Taura d 24 mscTaura d 32 msc

Tabla de contenido