PRESSURE CURVES/GAS DELIVERY

These curves show the gas pressure, in millibars, (at points Pi and Pt along the gas train)
necessary to produce a given delivery in m
burner working and with a pressure of 0 mbar in the combustion chamber. If the chamber
is pressurized, the gas pressure necessary will be that given in the diagram plus that in the
combustion chamber.
Legend
1 Interception cock - airtight at 1 bar and pressu-
re loss ≤ 0.5 mbar.
2 Vibration-damping joint
3 Gas pressure point for pressure reading
4 Gas filter
5 Gas pressure regulator
6 Minimum gas pressure control device (pressu-
re switch)
7 Class A solenoid safety valve.
Closure time Tc ≤ 1".
/h. The pressures have been measured with the
3
BASIC
GAS TRAIN
8 Class A solenoid adjustment valve, with slow
9 Gas delivery regulator, normally incorporated
10 Combustion head.
11 Minimum air pressure control device
12 Maximum gas pressure (over 350 kW) control
13 Tightness control device (on request)
Thermal output
Thermal output
33
opening or various stages and incorporated
gas delivery adjustment device. Closure time
Tc ≤ 1".
in either solenoid valve 7 or 8.
device (on request)
Legend
Pi Inlet pressure
Pt Pressure at
M
(combustion head +
gas train)
combustion head
UK