Pressure Switch - Lamborghini Caloreclima EM 3-E Manual Para La Instalación Y El Mantenimiento

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a drop in combustion air pres-
sure. It will be calibrated at a pressure below 1st stage rated-flow on-burner air pressure, checking that CO values do not
exceed 10,000 p.p.m..
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to shut it down if the gas pressure
falls below the minimum required level. This setting should be 40% lower than the gas pressure obtained with the burner
operating at maximum delivery.

PRESSURE SWITCH

Type: LGW 3 A2
LGW 10 A2
GW 50 A5
GW 150 A2
GW 150 A5a
Remove the cover and
adjust dial A
Air pressure switch
MODEL
EM 3-E
EM 6-E
EM 9-E
CHECKING CONTROL BOX IONIZATION CURRENT
The minimum value of 3 μA should be observed,
and large oscillations are to be avoided.
P r e s s u r e
connector
Setting range mbars
DUNGS type
LGW 3 A2
0,4 - 3
LGW 10 A2
1 - 10
LGW 10 A2
1 - 10
MICROAMPEREMETER CONNECTION
- 39
Gas pressure switch
DUNGS type
GW 50 A5
GW 150 A2
GW 150 A5
GW 150 A2
GW 150 A5
-
Setting range mbars
5 - 50
5 - 150
5 - 120
5 - 150
5 - 120
Tabla de contenido
loading

Este manual también es adecuado para:

Em 6-eEm 9-e

Tabla de contenido