OPERATING AND MAINTENANCE MANUAL
SPEEDBOX SERIES ELECTRONIC VARIATOR
14. GROUP MOUNT ALARMS:
The alarms, in the case of group mounting, are analogous to those of individual mounting
with the peculiarities of operation with 2 communicating devices. Depending on the system
reaction, there are 3 types of alarm:
1.- COMMUNICATION ERROR: no alarm is activated. Both devices continue to function
independently as SPEEDBOX. Neither device will show a flashing LED.
2.- MINIMUM LEVEL IN THE TANK: the water failure alarm is activated, but the device
remains deactivated.
It will automatically reset when the level sensor detects water again.
3.- REST OF ALARMS: if the alarm has occurred in only one device, the other will act as
the main one, only an attempt is made to start the failed device in case of over-demand,
after 4 successive alarms the device will be deactivated, must be reset manually. In the
case of alarms on both devices, the system makes 4 attempts to restore operation; if
unsuccessful, it will be deactivated. To manually restore a device deactivated by an alarm,
press AUTOMATIC ON/OFF on the MASTER and then ENTER on the affected device.
15. REGISTRATION OF FUNCTIONS AND ALARMS
By simultaneously pressing the MENU + keys for 3" you access the function and alarm log,
advance the log using the ENTER button, and when you finish the last log you return to the
main menu by pressing ENTER again. The display sequence is as follows: