OPERATING AND MAINTENANCE MANUAL
SPEEDBOX SERIES ELECTRONIC VARIATOR
In the case of group assembly, after pressing AUTOMATIC on the MASTER device, the
AUTOMATIC led on the SLAVE device will begin to flash intermittently, indicating that
there is communication between both devices. If this does not happen,
check the connections (fig.5).
11. ON SCREEN DISPLAY
With the device in automatic mode (LED AUTO ON), the different operating parameters can
be displayed using the cursor. Where:
•
P is the set pressure in bar.
•
P is the instantaneous pressure reading in bar.
•
Hz is the motor rotation frequency in Hz.
•
A is the instantaneous current consumed in A.
•
ºC is the temperature of the module in ºC.
12. INDIVIDUAL MOUNT ALARMS
To view the possible alarms accumulated in the system, exit the automatic operating mode
by pressing AUTOMATIC ON/OFF (the PUMP LED will turn off). Using the key
different accumulated alarms will be displayed. Once displayed, press ENTER to exit the
alarm manager returning to MANUAL operating MODE.
A1 LACK OF WATER (
DESCRIPTION When the system detects a lack of water in the suction for more than
10 seconds, it will stop the pump and the ART (Automatic Reset Test) system will be
activated.
SYSTEM RESPONSE After 5 minutes the ART system will run the pump again for 30
seconds, attempting to restart the system. If the lack of water persists, it will try again
every 30 minutes for 24 hours. If after this period, the system continues to detect a lack of
water, the pump will be permanently out of service until the problem is corrected.
Failure verification
19
Definitive failure)
the