6. Commissioning, operation
6.2 Electrical mounting
Only use original accessories. For accessories see data sheet PE 81.61.
WARNING!
The instrument shield does not act as a protective conductor for protection of personnel, rather as a
functional ground in order to shield the instrument from electromagnetic fields.
6.2.1 Connection assembly
For instruments with ratiometric output signals, a shielded cable must be used. The cable shield must be grounded,
if the cable is longer than 30 m or leaves the building.
Use a cable with suitable characteristics for the particular operating conditions.
For cable variants, strain relief must be employed.
Cable with ventilation tubes must be vented to atmosphere.
The instrument must be earthed via the process connection!
Select a cable diameter that matches the cable gland of the plug. Make sure that the cable gland of the mounted
plug has a tight fit and that the seals are present and undamaged. Tighten the threaded connection and check that
the seal is correctly seated, in order to ensure a tight seal.
For cable outlets, make sure that no moisture enters at the cable end.
Specifications for the assembly configurations of the mating connectors
Mating connectors for electrical connection Wire cross-section
Angular connector DIN 175301-803 A
Angular connector DIN 175301-803 C

6.2.2 Pin assignment

Circular connector M12 x 1 (4-pin)
U
+
U -
S
+
Shield
WIKA operating instructions pressure transmitter, model S-20
max. 1.5 mm
max. 0.75 mm
2-wire
3-wire
1
1
3
3
-
4
Case
Case
Cable diameter
6 ... 8 mm
2
4.5 ... 6 mm
2
Heavy-duty connector
U
+
U -
S
+
Shield
2-wire
3-wire
1
1
2
2
-
3
Case
Case
17
GB