L.B.White Sentry ST80 Manual Del Usuario E Instrucciones página 26

Soltera y dos etapa calentadores de tubo radiante
Ocultar thumbs Ver también para Sentry ST80:
Idiomas disponibles

Idiomas disponibles

26
Sentry Tube Heaters
specified on the dataplate? If so, then no further
checking or adjustment is required. Proceed to
section C.
3. If the inlet pressures do not agree with that speci-
fied on the dataplate, then the regulator controlling
gas pressure to the heater requires adjustment.
4. If the inlet pressure is correct but the burner mani-
fold pressure does not agree with that specified on
the dataplate, then the pressure regulator internal
to the gas control requires adjustment. Refer to
the following instructions. The burner box will need
to be opened and closed/latched as needed to
accurately set the gas control pressures.
5. If manifold gas pressure is different than dataplate,
remove the internal pressure regulator cap and
adjust the internal pressure regulator clockwise or
counter clockwise. See Fig. 31
C. Completion
1. Close the fuel supply valve to the heater and allow
the heater to burn off any remaining fuel.
2. Disconnect the heater from its electrical supply.
3. Remove the gauges and associated hardware.
Install plugs in gas control valve and in connector.
Tighten all securely.
4. Reconnect hose and adapter to sediment trap.
tighten securely.
5. Open fuel supply valve and reconnect electrical
supply to heater. Start the heater and check for gas
leaks. Set thermostat to desired temperature.
Owner's Manual • Sentry
loading

Este manual también es adecuado para:

Sentry st60Sentry st100Sentry st125