Red blink code of
signal lamp (LED))
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
14 blinks
CALCULATION OF WORKING OUTPUT OF THE BURNER
To calculate the burner's working output, in kW, proceed as follows:
- Check at the meter the quantity of supplied litres and the duration,
in seconds, of the reading, then calculate the burner's output through
the following formula:
1 - PUMP
2 - SAFETY OIL VALVE
3 - OIL VALVE
4 - RETURN VALVE
5 - NOZZLE
6 - GAS PRESSURE SWITCH
7 - SAFETY GAS VALVE
8 - GAS VALVE
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH
Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal feed pres-
sure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for L.P.G. nom.
pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw up cover M
ADJUSTMENT OF THE AIR PRESSURE SWITCH
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by tur-
ning regulator D to position 1.
- Start the burner and keep in low flame running, while checking that combustion is correct.
Through a small cardboard, progressively obstruct the air intake until to obtain a CO2 increa-
se of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressure port E, until rea-
ching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the adjustment value of
the air pressure switch until to have the burner lockout. Remove the obstruction from the air
intake, screw on the cover C and start the burner by pressing the control box rearm button.
Note: The pressure measured at pressure port E must be within the limits of the pressure
switch working range. If not, loose the locking nut of screw F and gradually turn the same:
clockwise to reduce the pressure; counterclockwise to increase. At the end tighten the locking
nut.
Error code table
«AL» at
Possible cause
term. 10
on
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
on
«LP» faulty
- Loss of air pressure signal after «t10», - «LP» welded in normal position
on
Extraneous light when burner is started up
on
Time out «LP»
- «LP» welded in working position
on
Free
on
Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
on
Free
on
Free
off
Wiring error or internal error, output contacts, other faults.
on
CPI contact not closed
GAS CIRCUIT
420010243004 MULTICALOR 170.1-200.1 PR/PR
e x f = kW
s
VGS
6
7
VgS
1
2
Suction
A
Return
R
VgR
4
pag.21
e =
Litres of gas
s =
Time in seconds
G20 = 34,02
G25 = 29,25
f
G30 = 116
G31 = 88
VG
8
Vg
3
5
gas pressure
switch
N
M
I
L
air pressure switch
D
C
A
G
B
EN
H
E
F