17. Insert the new dryer and tighten the screw to max. 15 Nm.
18. Reconnect the power plug.
19. Switch on the A/C service unit.
The inverter performs a self­test.
20. Reset the R1234yf from system counter (Resetting the counters on page 29).
21. Perform a leak test (Leak test on page 29).
14.5 Entering the filter code
To reset the filter counter, you need to enter a 12­digit code. This special code is located on the new filter. A Code
entry prompt appears in the menu. If a code is not entered, the A/C service unit is taken out of operation. Each
code only works once.
14.6 Calibrating the pressure transducer
The pressure transducer has to be correctly calibrated in order to make accurate pressure measurements. Cali­
bration is required:
• Every four weeks
• If the A/C service unit has been subjected to heavy shaking
• Every time the vacuum pump oil is changed
• If the display shows implausible pressure readings
1. In the basic menu use the cursor keys   or   to select Other selections.
Short selection
Free selection
Other selections
ENTER‐OK
2. Depressurize the A/C service unit (as described in chapter Changing the dryer filter on page 31.
3. Press 
ENTER
 to confirm.
4. Use the cursor keys   or   to select  Service
Service.
5. Press 
ENTER
 to confirm.
6. Enter the password 
2224
7. Confirm  Pressure transducer by pressing 
The device evacuates the service hoses.
8. Unscrew the service couplings from the service hoses (7) and (8).
9. Press 
ENTER
 to confirm.
‐‐‐‐
.