7. Press
ENTER
WARNING !
Usage only with
R ‐ 513A
ENTEROK
The A/C service unit runs a cleaning phase of the internal vessel pressure.
Cleaning phase.
Internal vessel
pressure mb.
Afterwards the A/C service unit runs a software test.
Please wait!
Software test.
Don't connect to
the A/C system yet!
Afterwards the A/C service unit displays the Standby menu:
Refrigerant
PAG oil
UV tracer
11:56:35
12.3 Setting the length of the service hoses
Note
• If longer or shorter service hoses are required for the unit, you have to adjust the filling quantities to
the new hose lengths.
• The service hoses for the high and low pressure sides must always be of the same length as other
wise the filling quantities will not be correctly measured.
1. In the basic menu use the cursor keys or to select Other selections.
Short selection
Free selection
Other selections
ENTER‐OK
2. Press
ENTER
3. Use the cursor keys or to select Service
Service.
4. Press
ENTER
5. Enter the password
6. Enter the hose length in centimetres.
7. Press
ENTER
12.4 Selecting the language
1. Press the cursor keys or .
2. In the basic menu use the cursor keys or to select Other selections.
12
to confirm the displayed refrigerant:
!
g.
ml
ml
10/03/17
to confirm.
to confirm.
.
7732
to confirm.
XXXX
XXX
XXX
‐‐‐‐