1.6 Electrical Installation
Pinout for the connector can be found in chapter "Connector Pinout" from (➜ # 205). Pinout
of the servo amplifier's end can be found in the instructions manual of the servo amplifier.
1.6.1 Important notes
Only staff qualified and trained in electrical engineering are allowed to wire up the motor.
Always make sure that the motors are de-energized during assembly and wiring, i.e. no
voltage may be switched on for any piece of equipment which is to be connected.
There is a risk of death or severe injury from touching exposed contacts. Ensure that the
switch cabinet remains turned off (barrier, warning signs etc.). The individual voltages will
only be turned on again during setup.
Never undo the electrical connections to the motor while it is energized. Risk of electric
shock! In unfavorable circumstances, electric arcs can arise causing harm to people and
damaging contacts.
A dangerous voltage, resulting from residual charge, can be still present on the capacitors
up to 10 minutes after switch-off of the mains supply. Even when the motor is not rotating,
control and power leads may be live.
Measure the DC-link voltage and wait until it has fallen below 60V.
l
The ground symbol
provide an electrical connection, with as large a surface area as possible, between the unit
indicated and the mounting plate in the switch cabinet. This connection is to suppress HF
interference and must not be confused with the PE (protective earth) symbol
measure to EN 60204).
To wire up the motor, use the wiring diagrams in the Installation and Setup Instructions of the
servo amplifier which is used.
DANGER
Dangerous voltage!
, which you will find in the wiring diagrams, indicates that you must
AKM Installation | 1 English