C C h h a a p p t t e e r r 3 3 U U P P S S I I n n s s t t a a l l l l a a t t i i o o n n
3 3 . . 1 1
M M o o u u n n t t i i n n g g t t h h e e U U P P S S t t o o t t h h e e D D I I N N R R a a i i l l
The EATON DIN24240DC and DIN24480DC UPS can be mounted on "top hat" 35mm DIN rail in accordance with EN60715.
To Mount the UPS:
1.
Locate the top hook of the DIN rail mounting system on the unit with the unit slightly titled.
2.
Rotate the unit till the latch of the rail mount system snaps on to the bottom of the DIN rail and the unit
cannot be rotated any further.
3.
Shake the UPS slightly to ensure that it is secure.
4.
Check if the UPS is facing upright and not tilting downward.
Figure 3. Mounting the UPS
A A d d j j u u s s t t i i n n g g t t h h e e D D C C U U P P S S o o n n t t h h e e D D I I N N R R a a i i l l
To adjust the UPS:
1.
To adjust the spacing between the DC UPS and EBMs, pull down the on the DIN rail clamp with a flathead
screwdriver or tool to release the clamp.
2.
Tilt up slightly and adjust to desired spacing and snap back onto DIN rail.
3.
Shake the UPS slightly to ensure that it is secure.
Hook to top of the DIN rail
NOTE
Maintain 0.39in (10mm) between devices, 1.97in (50mm) above, and 7.09in (180mm)
below.
Listen for a click to ensure the UPS is secured
to the DIN rail.
Eaton Din Rail UPS Advanced User Guide 934139—Rev A
5