Only qualified service personnel (such as a licensed electrician) should perform the electrical installation. Risk of
electrical shock.
The circuit breaker or disconnect switch must also be OFF at the DC input service panel.
To install the DC input / output wiring to the UPS:
1.
Locate the DC Input / Output terminal blocks on the front of the UPS.
2.
Ensure that the proper wire gauge is being used per
3.
Attach the DC +positive and —negative wires to the terminal block and torque to the specification.
Table 1. Recommended DC Input and Output Wire Sizes
Terminal
DC Input/Output
Recommended Wire Gauge
DIN24240DC
16 (1.5)
DC to UPS Input
+
-
DIN24240DC / DIN24480DC Input Wiring
Table 1
.
AWG (mm2)
DIN24480DC
12 (4)
DC to UPS Load
-
+
Eaton Din Rail UPS Advanced User Guide 934139—Rev A
Torque N-m (in-lb)
0.6 (5.3 in-lb)