2. OUTDOOR UNIT INSTALLATION
2-1. INSTALLING THE UNIT
• Be sure to fix the unit's legs ith bolts hen installing it.
• Be sure to install the unit firmly to ensure that it does not fall by an earthquake or a gust.
• Refer to the figure in the right for concrete foundation.
• Do not use the drain socket and the drain caps in the cold region. Drain may freeze and it makes the fan stop.
Make the setting
depth deeper.
2-2. CONNECTING IRES FOR OUTDOOR UNIT
• Be sure to use special circuits for room air conditioner.
• Wiring ork should be based on applicable technical standards.
• Wiring connections should be made follow ing the diagram.
• Screw s should be tightened so they w on't loosen.
1) Remove the service panel.
2) Remove the conduit plate.
3) Attach the conduit connector to conduit plate ith lock nut then secure
it to the unit w ith screw s.
4) Connect ground w ires to the TB support.
5) Loosen terminal scre , and connect indoor/outdoor unit connecting
ire (B) from the indoor unit correctly on the terminal block. Be careful
not to make mis- iring. Fix the ire to the terminal block securely so
that no part of its core is appeared, and no external force is conveyed
to the connecting section of the terminal block.
6) Firmly tighten the terminal scre s to prevent them from loosening. After
tightening, pull the ires lightly to confirm that they do not move.
7 ) Perform 5 ) and 6) for each indoor unit.
8) Connect po er supply cord (A).
9) Close the service panel securely. Make sure that 3-2. PIPE CONNEC-
TION is completed.
Connecting order
• Connect the terminal block in
follow ing order.
A → B → C → D → P
D unit is for 4C36NA3 only
Remar
* A disconnect s itch should be required. Check the local code.
* * Use a ring tongue terminal in order to connect a ground w ire to terminal.
INDOOR UNIT
Terminal block
Grounding
terminal * *
208/230 VAC
1 phase 60 Hz
Disconnect
sw itch *
Grounding
terminal * *
Terminal block
A – C D
D unit is for 4C36NA3 only
Fix here w ith
M10 bolts.
Make ith ider.
Pow er supply
Terminal block for
indoor/outdoor unit
5/8 in.
A – C D
1-3/8 in.
(15 mm)
(35 mm)
Terminal block
Lead w ire
Pow er supply
208/230 VAC
1 phase 2 w ires 60 Hz
GR
Terminal block
Terminal block 1
OUTDOOR UNIT
Anchor leg
Anchor bolt length
Anchor bolt pitch
ELECTRICAL SPECIFICATIONS
MXZ-3C24NA3
OUTDOOR UNIT
Po er supply (V, PHASE, Hz)
Max. Fuse size (time delay ) (A)
Min. Circuit Ampacity (A)
Fan motor (F.L.A)
(R.L.A)
Compressor
(L.R.A)
Indoor unit-Remote controller : (Wireless)
Control voltage
Indoor unit-Outdoor unit : DC12-24V
Screw s
Service panel
C o n n e c t w i re s t o t h e m a t c h i n g n u m b e rs o f t e rm i n a l s .
B e s u re t o a t t a c h e a c h s c re w t o i t s c o rre s p o n d e n t t e rm i n a l w h e n
s e c u ri n g t h e c o rd a n d / o r t h e w i re t o t h e t e rm i n a l b l o c k .
CONNECTING IRES AND CONNECTING GROUND IRE
• Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.
• Use double insulated copper ire ith 600 V insulation.
• Use copper conductors only .
*
F o l l o w
l o c a l e l e c t ri c a l c o d e .
PO ER SUPPL CABLE AND GROUND IRE
• Use solid or stranded conductor Min. AWG12.
• Use copper conductors only .
Grounding
*
F o l l o w
l o c a l e l e c t ri c a l c o d e .
terminal * *
ARNING
U s e t h e i n d o o r/ o u t d o o r u n i t c o n n e c t i n g w i re t h a t m e e t s t h e S t a n d -
ards to connect the indoor and outdoor units and fix the ire to the
Ground
t e rm i n a l b l o c k s e c u re l y s o t h a t n o e x t e rn a l fo rc e i s c o n v e y e d t o t h e
c o n n e c t i n g s e c t i o n o f t h e t e rm i n a l b l o c k . A n i n c o m p l e t e c o n n e c t i o n
or fixing of the ire could result in a fire.
For future servicing, give extra length to the connecting ires.
23-5/8
(600)
(Unit: inch (mm))
MXZ-3C30NA3
MXZ-4C36NA3
208/230, 1, 60
25
22.1
2.43
12
13.7
Conduit plate
Conduit connector
Lock nut
Conduit plate
e n
23.1
2.43
12
13.7
4