Expansion modules
Terminal resistance in kΩ
Interruption voltage in V
Maxiumum line resistance in Ω
Alarm threshold
Maximum response time in ms
Control outputs S1 - S3
Principle
Maximum voltage in V
Maximum over threshold voltage in V
Maximum current in mA
Control output S4
Principle
Minimum over threshold voltage in V
Minimum over threshold voltage in V
Maximum current in mA
Power output +12 V for external devices
Output voltage
Minimum output voltage
Maximum output voltage
Maximum output current in mA
When connecting an arming device (e.g. NBS 10 / coded arming device)
PL 1, 2, 5, 6 and S 1 - S 4
Primary line PL 3
Primary line PL 4
Terminal resistors for primary line PL 3
blocklock in kΩ
Terminal resistors for primary line PL 3 or PL
4 coded arming device in kΩ
Output current dependencies
Current at 12 V output 17/18 or 19/20 in mA Current at AUX 28 V 1/2 or 4/5 in mA
20
40
60
Bosch Sicherheitssysteme GmbH
12k1 for ISP-EMIL-120 and ISP-PCBA-
EMIL
4k7 for ISP-EMIL-3RDP
6
100
± 40% of terminal resistance
200
Open collector, active 12 V, 0 V switching
30
1.4
20
12 V switching
11.88
13.13
100, refer to Output current dependencies
+12.5 V DC ± 5%
11.88
13.13
100, refer to Output current dependencies
See above
Blocklock or coded
Coded arming device
4.7 ±1% (armed)
4.7 II 4.7 ±1% (unarmed)
4.7 ±1% (coded arming device invalid)
4.7 II 4.7 ±1% (coded arming device valid)
18