Instalación
36
Pares de apriete de tornillos máx. para AS 2129, tabla E
Diámetro nominal
[mm]
50
80
100
150
200
250
300
350
400
450
500
600
700
750
800
900
1000
1200
Pares de apriete de tornillos máx. para AS 4087, PN 16
Diámetro nominal
[mm]
50
80
100
150
200
250
300
350
375
400
450
500
600
700
750
800
900
Tornillos
[mm]
4 × M16
4 × M16
8 × M16
8 × M20
8 × M20
12 × M20
12 × M24
12 × M24
12 × M24
16 × M24
16 × M24
16 × M30
20 × M30
20 × M30
20 × M30
24 × M30
24 × M30
32 × M30
Tornillos
[mm]
4 × M16
4 × M16
4 × M16
8 × M20
8 × M20
8 × M20
12 × M24
12 × M24
12 × M24
12 × M24
12 × M24
16 × M24
16 × M27
20 × M27
20 × M30
20 × M33
24 × M33
Proline Promag W 400 EtherNet/IP
Par de apriete máx. [Nm]
HG
PUR
32
–
49
–
38
–
64
–
96
–
98
–
123
–
203
–
226
–
226
–
271
–
439
–
355
–
559
–
631
–
627
–
634
–
727
–
Par de apriete máx. [Nm]
HG
PUR
32
–
49
–
76
–
52
–
77
–
147
–
103
–
203
–
137
–
226
–
301
–
271
–
393
–
330
–
529
–
631
–
627
–
Endress+Hauser