Relay Output - EBARA Ego 2 slim Manual De Instalación Y Operación

Ocultar thumbs Ver también para Ego 2 slim:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

ELECTRICAL SPECIFICATIONS OF INPUTS, OUTPUTS AND COMMUNICATION
To see inputs, outputs and communication functions see chapter 5 Setup and operation. Some of the functions
are available only on Ego 2 slim and Module C. Detailed specifications about used protocols are described in
communications manual.
3.4.2.1 DIGITAL INPUT (RUN, 0V)
Ego 2 slim resistance of the closed loop
Only potential-free contact can be connected to this input.
3.4.2.2 ANALOG INPUTS AND OUTPUTS (SET1,SET2,SET3)
Only available in variant Ego 2 slim and Module C. U variant pumps only have an anlog 0-10V input. C variant
pumps have three connections that can be used either as inputs or outputs, depending on how we set it.
Input voltage
–1 - 32 VDC
Output voltage
Input impedance
Input sink current
Galvanic isolation

3.4.2.3 RELAY OUTPUT

Pump type
Rated current
MAX IIimum voltage
MAX IIimum power
3.4.2.4 ETHERNET
Only available in variant Ego 2 slim and Module C.
Connector
RJ-45, 10BASE-T, 10 Mbit/s.
-Web server (port 80)
Services
-Software update through web interface.
- Modbusa RTU through TCP/IP
Default IP address
192.168.0.245 (192.168.0.246 for right pump)
LED1
Ethernet
visual
diagnostics
LED2
Electrical properties
100 Ω
Electrical properties
When used as input.
0 - 12 VDC
When used as an output. MAX II. 5 mA load on individual output.
~100 kΩ
0.5 mA additional load for most configurations.
0 - 33 mA
Common sink on COM, if used as output.
Voltage 4 kV up to 1 s, 275 V permanent.
Electrical properties
Ego 2 (TC) slim < 850 W
3 A
250 VAC, 30 VDC
300 VA
Electrical properties
Slowly blinking if module is on. Lights up when the connection is established.
23
Ego 2 (TC) slim > 850 W
8 A
250 VAC, 30 VDC
500 VA
Tabla de contenido
loading

Tabla de contenido