5.2.2. Preparatory tasks
• Select installation location:
• Outside buildings
• Not in the immediate vicinity of living and sleeping areas
• Max. height adjustment with concrete rings: 200 mm
• Max. height adjustment with plastic pump chamber extension:
500 mm
CAUTION!
The pump chamber may not be installed in peaty ground.
This can lead to destruction of the pump chamber.
• Pump cover
• Must be ordered separately.
• Classes in accordance with EN 124: A15, B125 or D400
For class D400 a load distribution plate must be provided onsite.
• Load distribution plate:
Dimensions: External Ø: 1700 mm; Internal Ø: 700 mm; Thickness:
300 mm; Concrete grade: C 35/45; Reinforcement: Concrete steel
B500A 10 mm, spacing 150 mm longitudinal + lateral, up + down
5.2.3. Pump chamber installation
• Take into account the direction of the inlet, pressure and ventilation
connection.
• Take into account the cable length for the pump and level control
device, so that the pump and level control device can be lifted out of
the pump chamber.
• Have the pump cover ready.
Fig. 3: Pump chamber installation
1
Pump cover
2
Pump chamber extension
3
Pump chamber
4
Venting/cable ducts
5
Connection port DN 150
6
Connection port DN 200
7
Levelling layer
8
Underlay
46
X
Required pit depth
Y
Pump cover height
Z
Max. pump chamber diameter
1
2
3
4
5
5
7
8
Z
Z + 2000
Fig. 3
4
6
WILO SE 11-2015 V05 DIN A4