4
Mounting
4.1
Mounting the NCS to the part-turn actuator
Requirements
1. An EMC filter module in the positioner.
2. A non contacting sensor for part-turn actuators 6DR4004-.N.10 or 6DR4004-.N.40.
3. A part-turn actuator with interface to VDI/VDE 3845 and mounting console to VDI/VDE 3845, or a part-turn actuator with
manufacturer-specific interface.
NOTICE
Incorrect mounting
A clearance of 3 mm must be maintained between the magnet and the mounting console in order to ensure correct
measurement of the actuator position. The values transferred may be incorrect if this clearance is not given.
Maintain a clearance of 3 mm between the top edge of the magnet
•
⑩
.
Description
①
Tensioning ring
②
Hex socket head screw size M3x12
③
Spring element
④
Magnet
⑤
Hooks
⑥
Plastic washer
⑦
Hex socket head screw size M6x12
Figure 4-1
Mounting on part-turn actuator with magnet holder made of glass fiber reinforced polyester (left graphic) or
anodized aluminum (right graphic)
Procedure for the part-turn actuator to VDI/VDE 3845
1. Slide the clamping table
2. Mount the clamping table
3. Depending on the material of the magnet holder, proceed as follows:
8
All manuals and user guides at all-guides.com
⑨
onto the stub shaft of the part-turn actuator.
⑨
to the stub shaft using a hex socket head screw
④
and the top edge of the mounting console
⑧
Washer
⑨
Clamping table
⑩
Mounting console
⑪
Hexagon nut
⑫
Hex socket head screw size M6x25
⑬
Non Contacting Sensor (NCS)
⑦
and washer
SIPART PS2 Non Contacting Sensor (NCS)
⑧
.
A5E00097485-09, 09/2014