5
Connecting
NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
Before installing ensure there is no visible damage to the device.
•
Make sure that process connectors are clean, and suitable gaskets and glands are used.
•
Mount the device using suitable tools. Refer to the information in Technical specifications (Page 15) for installation
•
torque requirements.
Requirements
You need the EMC filter module with article number C73451-A430-D23 to connect the NCS to the positioner. The positioner
supplies auxiliary power to the NCS via the EMC filter module.
Wiring diagram
①
Positioner (open state)
②
Vcc: Yellow
③
Vref: Green
④
Vpos: Black
⑤
Ground: Brown
⑥
EMC filter module C73451-A430-D23
Figure 5-1
Example of connecting the NCS to the EMC filter module
Procedure
The NCS is equipped with a shielded four-pole cable. Wire this cable to the positioner as follows:
1. Feed the four-pole NCS cable
the positioner version.
SIPART PS2 Non Contacting Sensor (NCS)
A5E00097485-09, 09/2014
All manuals and user guides at all-guides.com
⑩
through the union nut and the cable gland. Note: The type of cable gland depends on
⑦
Cable clamp
⑧
Screw F3x8
⑨
Cable gland
⑩
Four-pole NCS cable
⑪
Non Contacting Sensor (NCS)
⑫
Cable shielding lug
13