Premium EPS-120-5192 Manual De Operación página 14

Ocultar thumbs Ver también para EPS-120-5192:
Idiomas disponibles

Idiomas disponibles

Classification
Group
Urgent Failure
1
Non-urgent
2
failure
3
Events
Other events
4
High
5
occurrence
www.premiumpsu.com
Powering Your Challenge
Table 3.7 - Recorded events
Type
Name
1
Charger failure
2
High Temp
3
Battery Absent
4
Test failure
101
Charger OK
102
Normal charger temperature
103
Battery present
1
Voutput 1 High
2
Voutput 1 Low
7
Battery voltage High
8
Bat Temp High
9
Temp Bat Low
10
Temp Probe Failure
101
Output voltage Normal
107
Battery voltage normal
108
Battery temperature normal
110
Temperature Probe Normal
1
Vmains Absent
2
Vmains Low
3
End of Autonomy
4
Battery connection attempt
101
AC Input Mains Voltage Normal
1
Power UP
2
Overload
5
Limitation due to Temp.
6
Quick charging
7
Discharging
8
Floating
9
Battery charged
10
Battery test
11
Test OK
12
Forced: Local
13
Forced: Battery
1
14
Forced: Test
15
Forced: Quick charging
16
Forced: Floating
17
Forced: Battery charged
18
Forced: Battery reconnection
19
Forced: Reset Device
20
Forced: Factory parameters
21
Forced: AC error relay
22
Forced: End of Autonomy Relay
23
Forced: Non-urgent failure relay
24
Forced: Urgent failure relay
25
System alarms acknowledged
26
Daylight saving time activated
27
Daylight saving time de-activated
28
Forced: starting from push button
29
Forced: Switching main output off
1
NTP Failure
2
SNMP Failure
Communications' Operation Manual
Description
Internal device malfunction.
High device temperature.
Battery not available.
Periodic battery test result: failed.
Charger is operating correctly
Normal device temperature
Battery available
Output voltage outside range: Overvoltage.
Output voltage outside range: Undervoltage.
Battery voltage outside range: overvoltage
High battery temperature.
Low battery temperature.
Temperature sensor not detected.
Main output voltage within the range.
Battery voltage within the range
Battery temperature normal
Temperature sensor normal.
No AC input voltage.
AC input voltage outside range: Undervoltage.
Battery empty.
Battery connection detected with bat = "0".
There is AC input voltage.
Starting the device.
Device in overload.
Power limitation due to high temperature of the device.
Battery on quick charge.
Battery discharging.
Battery floating.
Battery charged.
Battery test in progress.
Result of periodic battery test: OK.
Local IP forced from push button.
Battery reconnection forced from push button.
Battery test forced.
Forced into quick charging.
Forced into floating.
Forced into battery charged.
Battery absence test forced
Force a restart of the device.
Force the loading of default parameters.
Force activation of input mains failure relay.
Force activation of the end of autonomy relay.
Force activation of non-urgent failure relay.
Force activation of urgent failure relay.
The system has acknowledged (ACK) all alarms.
It has switched to daylight saving time.
It has switched to winter time.
Starting the device from the battery using a push button.
Force switching off of main output for 5s
Failure in connecting to the NTP server.
Failed in sending TRAP SNMP.
EPS Series
MA-5192B-1
07-10-2021
/
14
77

Capítulos

loading

Productos relacionados para Premium EPS-120-5192

Este manual también es adecuado para:

Eps-200-5193