Panasonic Urban Multi CS-20UMHPP Manual De Instalación Y Funcionamiento página 7

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 42
Next, press the inspection/test operation button
remote controller. The unit will engage the test operation mode.
Press the operation mode selector button
fan operation
. Then, press the on/off button
unit fan and drain pump will start up. Check that the water has
drained from the unit. Press
E
LECTRIC WIRING WORK
General instructions
All field supplied parts and materials and electric works must
I
conform to local codes.
Use copper wire only.
I
I
Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
All wiring must be performed by an authorized electrician.
I
A circuit breaker capable of shutting down power supply to the
I
entire system must be installed.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
I
This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and HR box are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.
Electrical characteristics
Model
Hz
CS-20~125UMHPP
50
power supply
MCA
CS-20~50UMHPP
0.5
CS-63UMHPP
0.6
CS-80UMHPP
1.0
CS-100UMHPP
1.1
CS-125UMHPP
1.4
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
NOTE
For details, refer to "Electrical data".
Specifications for field supplied fuses and wire
Model
Field fuses
CS-20~125UMHPP
16A
Model
CS-20~125UMHPP
Sheathed wire (2)
CS-20~125UMHPP
Urban Multi air conditioner
4PW12338-1A
on the
TEST
until selecting
. The indoor
to go back to the first mode.
TEST
Volts
Voltage range
230
min.198-max.264
Fan motor
MFA
KW
FLA
16A
0.045
0.4
16A
0.045
0.5
16A
0.090
0.8
16A
0.090
0.9
16A
0.090
1.1
Power supply wiring
Wire
Size
H05VV-U3G
Local codes
Transmission wiring
Wire
Size
2
0.75-1.25 mm
For details, refer to the chapter "Wiring example".
NOTE
I
Allowable length of transmission wiring between
I
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:
Outdoor unit - indoor unit: max. 1000 m
(total wiring length: 2000 m)
Indoor unit - remote controller: max 500 m
W
IRING EXAMPLE AND HOW TO SET THE
REMOTE CONTROLLER
How to connect wiring
(See figure 12)
I
Power supply wiring
Remove the switch box lid (1) and connect the wires to the
power supply terminal board inside. While doing this, pull the
wires inside through the rubber bush A and clamp the wires
along with other wires using clamp A, untightening the clip of
clamp A by pressing. After the connection, tighten clamp A as
before.
Unit wiring and remote controller wiring
I
Remove the switch box lid (2) and pull the wires inside through
the rubber bush B and connect to the terminal board for unit
transmission wiring.
I
After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.
1
Switch box lid (1)
2
Power supply
3
Power supply terminal board
4
Rubber bush A
5
Clamp A
6
Switch box lid (2) with wiring diagram label
7
Transmission wiring
8
Terminal board for transmission wiring
9
Rubber bush B
Clamp B
10
Outside of the unit
11
12
Inside of the unit
13
Cable (power supply or transmission wiring)
14
Opening for the cable
15
Small sealing
Precautions
1
Observe the notes mentioned below when wiring to the power
supply terminal board.
Do not connect wires of different gauge to the same power supply
terminal. (Looseness in the connection may cause overheating.)
When connecting wires of the same gauge, connect them
according to the figure.
Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. (tightening torque 1.31 Nm ±10 %)
Installation and operation manual
5
Tabla de contenido
loading

Tabla de contenido