CONVECTOR
MOTOR
DISCONNECTED.
EXTRACTION
MOTOR
DISCONNECTED.
ENDLESS
MOTOR
DISCONNECTED.
ELECTRODE
(START-UP
RESISTANCE)
DISCONNECTED.
CONVECTOR MOTOR IN
SHORT-CIRCUIT.
SHORT-CIRCUIT OF THE
EXTRACTION MOTOR.
ENDLESS MOTOR SHORT-
CIRCUIT.
necessary for combustion to happen.
The C.P.U. does not detect the Convector.
The C.P.U. does not detect the Extractor.
The C.P.U. does not detect the reduction
motor of the endless motor.
The C.P.U. does not detect the start-up
Electrode (start-up resistance).
The Unicontril detects that the convector or
the
output
voltage
corresponding to the convector is in short-
circuit.
The C.P.U. detects that the Extractor of
tension outlet of the C.P.U. corresponding to
the extractor is in short-circuit.
The C.P.U. detects that the reduction motor
or tension output of the C.P.U. corresponding
to the reduction motor is in short-circuit.
Stove
maintenance.
Air entrance pipe stacked. Clean air Entrance
pipe.
Air reading pipe (transparent silicone pipe
linking the C.P.U. to the air inlet pipe),
disconnected or cut. Connect or replace.
Extractor does not turn.
Failure in depression reading system of the
C.P.U., check depression air level, cf. Menu 3,
chapter 1 (S.A.T.)
If the stove is new, this might be due to
electric power problems.
Check the convection motor is connected to
power through menu 3 section 0.
Check the grey cable going out from the
C.P.U. Connect it if necessary.
If the stove is new, this might be due to
electric power problems.
Check is power is being supplied to the
exhaust motor through menu 3 section 1.
Check the red cable going out from the C.P.U.
Connect it if necessary.
If the stove is new, this may be due to
electrical problems.
Check if the endless motor is connected to
power, see menu 3 section 2.
If power does not reach the endless motor,
check-with the stove disconnected- if the
safety thermostat is activated. Reactivate if
necessary.
If the stove is new, this might be caused by
electrical problems.
Make sure power reaches the start-up
resistance, see menu 3 section 3.
Check the black cable going out from the
C.P.U. Connect it if necessary.
If the stove is new, this might be caused by
electrical problems.
Check with a multimeter if the motor is
of
the
C.P.U.
clamped to earth or the winding is in short-
circuit. Make sure power reaches the
convection motor, see menu 3 section 0.
Check the grey cable going out from the
C.P.U. Connect it if necessary.
If the stove is new, this might be caused by
electrical problems.
Check with a multimeter if the motor is
clamped to earth or the winding is in short-
circuit. Make sure power reaches the
convection motor, see menu 3 section 1.
Check the red cable going out from the C.P.U.
Connect it if necessary.
Make sure power reaches the endless motor,
see menu 3 section 2.
Check with a multimeter if the motor is
clamped to earth or the winding is in short-
circuits.
Check the brown cable going out from the
C.P.U. Connect it if necessary.
44
full
of
ash
inside.
Carry
out