Pfannenberg DTS Serie Manual De Instrucciones página 72

Ocultar thumbs Ver también para DTS Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 168
GB
Error messages
Error
Fault
no.
Er06
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er07
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er11
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Operating Manual DTS and DTI 6X2E Premium Controller X-Series (XC) 086100099d © Pfannenberg GmbH
Unit activity
Possible causes
• Sensor 1 Minimum:
Blinking
• Minimum switch cabinet
0%
temperature value "Lit_"
100%
(LCD display)
is reached or exceeded.
0%
100%
Open
• Sensor 1 Maximum:
Blinking
• Maximum switch cabinet
100%
temperature value "Lit_"
100%
(LCD display)
is reached or exceeded.
• The cooling unit cannot
100%
0%
sufficiently cool the air in
Open
the switch cabinet.
• Sensor 3 (TS3) defect.
Blinking
According to
regulation
According to
regulation
100% , if
compressor 100%
0%
Open
Corrective measures
 Select higher switch
cabinet-
Select temperature
setpoint.
 Inspect the switch
cabinet for leaks.
 Move components near
the air intake and outlet
further away in order to
prevent an air short
circuit. (The cold air is
diverted directly to the air
inlet by components.)
 Check the settings of the
cooling unit.
 Clean the heat
exchanger fins
(internal/external).
 Evaporator fan
check (internally) for
function.
 Check the refrigeration
circuit for escaping
refrigerant or leaks.
 If necessary, install a
cooling unit with a higher
cooling capacity.
 Replace Sensor 3 or the
controller circuit board
according to the unit
type.
Page 31 / 42
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Dti 6x2e serieX serieXc serie

Tabla de contenido