GB
Error messages
Error
Fault
no.
Er06
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er07
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Er11
• LED:
• Compressor:
• Evaporator fan
(internal):
• Condenser fan
(external):
• Heater (external):
• Fault signal contact:
Operating Manual DTS and DTI 6X2E Premium Controller X-Series (XC) 086100099d © Pfannenberg GmbH
Unit activity
Possible causes
• Sensor 1 Minimum:
Blinking
• Minimum switch cabinet
0%
temperature value "Lit_"
100%
(LCD display)
is reached or exceeded.
0%
100%
Open
• Sensor 1 Maximum:
Blinking
• Maximum switch cabinet
100%
temperature value "Lit_"
100%
(LCD display)
is reached or exceeded.
• The cooling unit cannot
100%
0%
sufficiently cool the air in
Open
the switch cabinet.
• Sensor 3 (TS3) defect.
Blinking
According to
regulation
According to
regulation
100% , if
compressor 100%
0%
Open
Corrective measures
Select higher switch
cabinet-
Select temperature
setpoint.
Inspect the switch
cabinet for leaks.
Move components near
the air intake and outlet
further away in order to
prevent an air short
circuit. (The cold air is
diverted directly to the air
inlet by components.)
Check the settings of the
cooling unit.
Clean the heat
exchanger fins
(internal/external).
Evaporator fan
check (internally) for
function.
Check the refrigeration
circuit for escaping
refrigerant or leaks.
If necessary, install a
cooling unit with a higher
cooling capacity.
Replace Sensor 3 or the
controller circuit board
according to the unit
type.
Page 31 / 42