POSI-BBPR (GPS) : electric connection
The caps placed on M20x1.5 openings (p.27 mark 14) must be replaced by ATEX and IP68 metallic certified cable
glands. The unused threaded opening must be closed with ATEX and IP68 certified caps.
Power supply and control wiring

Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.

Unscrew the left cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 48.

Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Setpoint and feedback wiring

Unscrew the right gland and pass the cable.

Connect the input signal between terminals 15 and 16 (see p.46). Terminal 15 is the negative polarity (-) and terminal 16 is
the positive polarity (+).

Connect the output signal between terminals 13 (A or B) and 14 (see p.46). Terminal 13 is the positive polarity (+) and ter-
minal 14 is the negative polarity (-).

Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Factory setting : by default, 4-20mA input and output signals with normal rotation sense.

Learning mode


Switch on the actuator

Press both OPEN and CLOSE buttons until the learning mode is selected, (APPR LED on).

Press CLOSE button. The valve operate into closed position.

When the valve is closed, press both CLOSE and MEM buttons during 2 seconds.

The APPR2 led blinks rapidly and then lights on. The closed position is stored.

Press OPEN button. The valve operate into open position.

When the valve is open, press both OPEN and MEM buttons during 2 seconds.

The APPR1 led blinks rapidly and then lights on. The closed position is stored

Exit the learning mode by simultaneously pressing the OPEN and CLOSE buttons to the POSI mode.
X
®
Thanks to A
MART
(via Bluetooth
the actuator will reach in case of power failure.
it's also possible to access to actuator parameters in real time, to schedule weekly tasks and to con-
trol it locally.
For any further information, refer to the operation manual with the reference DSBA3304.
Be sure you connect the terminal 15 (-) before the terminal 16 (+)
The battery charge cycle is automatically managed by the electronic card since the first power up. A CTN in
the battery pack and a fuse on the electronic card are present to ensure safety in the event of a short circuit or
excessively high temperature in the actuator .
Following a power failure, the BBPR unit will reset after 4 minutes.