Normal Operating Mode - Watts Valpes DVX 25 Serie Manual De Instalación Y Funcionamient

Idiomas disponibles

Idiomas disponibles

EN
POSI (GP5) : parameter selection sequence
K3 OFF
K3 ON
G
R
R
R
R
G
R
R
R
G
G
G
G
R
DSBA3801 • Rév. 02/06/2021
1 Shunts positioning K1, K2 and K3
Position the shunts as follows (before modification, switch off the card):
Setpoint
signal
0-10V
0-10V
0-10V
4-20mA
4-20mA
4-20mA
0-20mA
0-20mA
0-20mA
Selection of the flow direction of the valve
2.1 Normal flow direction (by default)
Press the OPEN button and apply the operating voltage to the card while keeping this
button pressed.

The green LED lights up. Release the OPEN button.

Disconnect the card.
2.2 Inverse flow direction

Press the CLOSE button and apply the operating voltage to the card while keeping this but-
ton pressed.

The red LED lights up. Release the CLOSE button.

Disconnect the card.
3 Selection of the type of input control signal
3.1 Voltage control signal 0-10V

Press the MEM button and apply the operating voltage to the card while keeping this but-
ton pressed.

The red LED will light up 3 times. Release this button.

Disconnect the card.
3.2 Current control signal 4-20mA (by default)

Press the MEM and CLOSE buttons and apply the operating voltage to the card while
keeping these buttons pressed.

The red LED will light up 3 times. Release these buttons.

Disconnect the card.
3.3 Current control signal 0-20mA

Press the MEM and OPEN buttons and apply the operating voltage to the card while
keeping these buttons pressed.

The red LED will light up 3 times. Release these buttons.

Disconnect the card.
4 Learning mode

Press the OPEN and CLOSE buttons and apply the operating voltage to the card while
keeping these buttons pressed.

The 2 LED will light up. Release these buttons and the 2 LED will extinguish. The card is
now in the learning mode.

Press the CLOSE button to put the valve in its closed position. The red LED will light up.

Store this selected closed position by pushing MEM + CLOSE, the red LED will light up 2
times as a confirmation of acknowledgement.

Press the OPEN button to put the valve in its open position. The green LED will light up.

Store this selected open position by pushing MEM + OPEN, the green LED will light up 2
times as a confirmation of acknowledgement.

Now, the positions selected have been stored. Disconnect the card.

NORMAL OPERATING MODE


Apply the operating voltage to the card. The green LED will light up 3 times.

Under normal operating conditions, the green LED will light up when the drive motor
opens the valve, and the red LED will light up when the drive motor closes it.

If both LED remain extinguished, it means that the drive motor has not been triggered.
In the case of an over torque, the motor stops and the 2 LED lights then together to indicate the
action of the torque limiter. To re-start it, you must either reverse the sense of rotation, either switch
the power off and on.
Schunt K1
Feedback
signal
A
B
0-10V
ON
OFF
0-20mA
ON
OFF
4-20mA
ON
OFF
0-10v
OFF
ON
0-20mA
OFF
ON
4-20mA
OFF
ON
0-10V
OFF
ON
0-20mA
OFF
ON
4-20mA
OFF
ON
Schunt K2
Schunt K3
A
B
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
ON