3.3.
Monitoring the parameters 
 
The 
or 
keys can be used to scroll through the parameters in either direction, the left‐hand digit (green) 
 
 
indicating  the  number  of  the  selected  parameter.  If  no  key  has  been  pressed  for  8  seconds,  the  display  returns  to 
normal. 
 
Note: if the parameters have not been validated using the switches, they will not appear during scrolling. 
 
4.
OPERATING MODE 
 
4.1.
Control 
Control doesn't start until at least 6 seconds after powering on the system, in order to let the pressure readings 
stabilize. 
 
If the control pressure reaches the low pressure value, the main motor is started (1
If the control pressure reaches the top‐up value, the top‐up motor is started (2
If the control pressure reaches the 3
rd
 backup pressure, the 3
If several motors have to be started at the same time, their start‐ups will be separated by 12 seconds, and their 
shutdowns by 2 seconds. 
At  each  control  cycle,  circular  switching  of  the  motors  takes  place  if  the  switch  (SW1‐8)  is  validated  (cyclic  motor 
switching). Otherwise (fixed motor allocation), motor A = priority, motor B = top‐up and motor C = 3
The  switch  SW1‐5  manages  the  selection  of  the  motors  switching  either  at  each  stop  or  after  60  minutes  ‐ 
cumulative time of the priority motor since the last switching. 
 
On/Off motor delay 
The  parameter  "r"  manages  the  temporization  of  the  pumps  starting  or  stopping,  when  pressure  thresholds  are 
exceeded.  The  order  of  starting  must  be  taken  into  account  when  the  low  threshold  is  exceeded,  and  a  vacuum 
pump  starts  at  the  end  of  "r"  seconds,  even  if  the  pressure  rises  above  this  threshold.  Temporization  is  started 
again for each passage of thresholds (low, top‐up and 3
 
Programming of the motors presence 
When a motor is breaking down, it can be inactivated with the parameter "motor presence". 
If the motor is inactivated, then its alarm is not generated, its hour meter is not incremented, its indicator "walk" is 
not lit, its order relay is not controlled. The red indicator "flashes" (100 ms every 2s). 
The cycle of motors switching is not modified in order to avoid the introduction of a particular management into 
the software. In this case the top‐up makes start the 2nd or 3rd motor if need be. 
It is forbidden that all motors are removed. 
Note: During the modification of one of the parameters "motor presence", the order of motors activation is reset 
(according to the motors installed). 
519112‐02 
CYCLIC 2020 
st
 motor). 
nd
 motor). 
rd
 backup motor is started (3
rd
 motor). 
rd
 backup. 
rd
 backup) 
On/Off  mode:  The  motor  starts  at  the  low 
pressure  value  and  stops  at  the  high 
pressure value. 
 
 
 
 
 
 
 
FLEXO mode: 
This mode is selected by the ON‐OFF / FLEXO input and when a motor starts running its operation will be forced 
for  the  minimum  time  period  set  by  the  switches  (SW2.2)  and  (SW2.1)  since  its  start‐up  without  taking  into 
account the high pressure control. Once this FLEXO period has elapsed, the motor will be able to stop once the 
control pressure has reached the high pressure value. 
Note:  FLEXO  mode  operating  time  must  be 
less than the top‐up time. 
 
FLEXO mode can be remotely controlled by 
opening  or  closing  the  ON‐OFF/FLEXO 
input. This allows operation in FLEXO mode 
when  there  is  a  high  demand  (e.g.  in  the 
morning)  and  in  ON‐OFF  mode  when 
demand is low (e.g. at night). Consult us for 
further details. 
 
With vacuum, if the network pressure reaches the high network alarm threshold ‐ 20 mbar, motors are stopped. 
Example: If the network high pressure alarm threshold = ‐880 mbar, then the motors stop at ‐900 mbar 
 
4.2.
Hygrometry: per‐line management or independent management 
4.2.1.
Per‐line hygrometry management 
In this configuration one air drier is assigned to 
one  air  compressor  and  they  are  operating  in 
phase with each other. 
4.2.2.
Independent hygrometry management 
In  this  configuration  there  are  only  two  air 
driers whatever the number of compressors, 
with  one  drier  in  service  and  the  other  as  a 
backup. 
 
 
 