Operations
MAIN MENU / SUBMENU
SETTINGS
Advanced setup
(continued)
ABOUT
UPS Information
Network ID
Firmware
Mobile Access
DOCUMENTATION
Documentation QR code
DISPLAY / SETTING OPTIONS
On battery:
• Low Batt. Alert
o Enter: 10-90% (factory setting is 20%)
• Timed Shutdown
o Enter: 15, 30, 45 sec., 1-30 min.
o Disable (factory setting)
• Low Battery Shutdown
o Enter: 5-100%
o Disable (factory setting)
• On Batt. Beep Delay
o Enter: 0-120 seconds
(factory setting is 5 seconds)
• Shutdown Completion
o Required (factory setting)
o Interrupt OK
DB9 Settings:
• DB9 Settings
o Output pins 1&5
- On battery (factory default)
- On bypass
- Output on
- Low battery (battery mode only)
o Output pins 8&5
- On battery
- On bypass
- Output on
- Low battery (battery mode only—
factory default)
o Input pins 3&9
- Shutdown (battery mode only—
factory default)
- Output off
- Reboot
- Output on
- Power Toggle
UPS model number, UPS Serial number,
UPS installed date
Web management accessory card firmware,
IPv4 address, IPv6 address, MAC Address
UPS firmware versions
—
—
DISPLAY / SETTING DESCRIPTION
Enables the UPS to send a low-battery alert as batteries discharge
to the selected charge level during a power failure.
Timed shutdown sets the maximum amount of battery runtime in
seconds or minutes the UPS will provide during a power failure.
Use the DISABLE setting for the longest possible battery runtime.
Low battery shutdown sets the maximum amount of battery
discharge before the UPS shuts down due to low battery. The
setting of DISABLE allows the batteries to discharge to 0% before
shutdown.
The "Beep Delay" setting allows the audible alarm to be delayed
up to 120 seconds to prevent the audible-alarm from sounding in
response to short duration power failures.
The UPS will communicate shutdown messaging to connected
systems prior to UPS shutdown. The setting of INTERRUPT OK will
interrupt shutdown messaging if power is restored after shutdown
messaging is sent.
The UPS will signal the selected condition by shorting pins 1 and
5 on the DB9 port. The max voltage and current flow through this
dry contact connection is 30VDC 10mA.
The UPS will signal the selected condition by shorting pins 8 and
5 on the DB9 port. The max voltage and current flow through this
dry contact connection is 30VDC 10mA.
The UPS will perform the selected action when pins 3&9 are
shorted on the DB9 port for at least 4 seconds.
For the Reboot option (output off for 30 seconds before reboot):
Note the pins must be shorted for at least 4 seconds to perform
the reboot. The reboot happens at exactly 4 seconds. If the pins
continue to be shorted for more than 4 seconds, no further action
should be taken. The UPS takes no action on release of the short.
The Power Toggle option is intended to keep the unit powered on
whenever the pins are not shorted and powered off whenever the
pins are shorted. Note this input cannot power on the unit from an
off state unless valid AC is applied (this function will not impose a
coldstart). To power on, the pins must be not shorted for at least
4 seconds and AC must be valid. To power off, the pins must be
shorted for at least 4 seconds.
UPS installed date is automatically set by the unit after 2 hours of
continuous operation.
Directs user to the SNMP card interface. The URL is secure
HTTPS.
Directs user to product documentation on the Tripp Lite website.
29