Indoor fan characteristics with HPD accessory
Motor
(1)
Model
Type of
kW
casing
120
4
100LC
150
5.5
112MB
180
5.5
112MB
240
7.5
132M
300
11
132MB
360
11
132MB
480
15
160L
(1) All motors are totally enclosed, fan-cooled, run at 1450 r.p.m., have a solid base and a 1.15 service factor.
Indoor fan performances
- For cool only units with 0% outdoor air
and 100% return, dry indoor coil and EU3
standard air filters.
- Attention: Before going to the tables, do
not forget to add to the pressure needed
in the installation the pressure drop due
to the gas or pump unit model, the vertical
impulse and return, and the accessories
included in the unit.
- The motor pulley is factory-adjusted to 4
opening turns. See Pulley adjustment and
belt tensing section.
- Attention: Upon commissioning the unit
and having balanced air distribution in
the conditioned area, the impulse air flow
must be checked.
It is very recommendable to not go over a
depression of -200Pa at indoor fan suction
with clean filters.
Checking impulse air flow
Turn the impulse air fan motor on.
Adjust resistance in the impulse and return
to balance air distribution throughout the
conditioned area. Due to the specifications
of the site, it may be necessary to have this
balancing process carried out by someone
indicated by the installer.
To check impulse air flow after initial
balancing:
1. There are two 9.5 mm. holes for reading
the pressure in front of and behind the
evaporating coil.
They are located on the filter and fan
side access panels, and have a caps.
Fig. 3.
2. Insert at least 200 mm. of pipe (with a
diameter of about 6 mm.) in each hole
to achieve sufficient penetration in the
air flow on both sides of the indoor coil.
14
Motor pulley (adjust-
Fan pulley (fixed)
able)
Pulley Ø
Shaft Ø
Pulley Ø
(mm.)
(mm.)
(mm.)
-
-
132
-
-
160
147-178
28
-
147-178
38
-
152-190
38
-
152-190
38
250
152-190
42
250
Note:
The pipes should be inserted and
kept in perpendicular to the air
flow so that the pressure of the
speed does not affect the static
pressure reading.
3. Using an inclined pressure gauge, deter-
mine the pressure drop in the dry indoor
coil. As humidity may vary considerably
in an indoor coil, any measurement of
a humid coil in site conditions would be
inaccurate.
To be sure the coil is dry, disconnect the
Location of the holes (pressure drop reading) (Models 90 - 300)
Belt
Shaft Ø
Length
Ref.
(mm.)
(mm.)
25
1 360
BX52
25
1 490
BX57
-
1 790
BX69
-
2 040
BX79
-
2 040
BX79
25
1 790
BX69
25
1 840
BX71
�����
��������
�������
������
��������
����������
�����������
��������������������
��������������
Fig. 3
GB
Nominal
Motor
amperage
guard
(A)
range
Amount
1
8.6
6.3-10
1
11.4
9-14
1
11.4
9-14
1
14.8
13-18
2
21
20-25
2
21
20-25
2
29
22-32
compressors while running this test.
4. Knowing the pressure drop of a dry coil,
the real air flow going through the unit
can be determined by the curve that
appears in Fig. 4.
Once all readings have been made, remove
the pipes and replace the caps on both
holes.
Warning:
Not being able to adjust the total
amount of air in the system could
cause serious damage to the
fan.
������
����
�������������
Regu-
lation
In+10%
(A)
9.5
12.5
12.5
16
23
23
32