WARNINGS:
• This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
• Materials of construction are chosen based on their chemical compatibility (or
inertness) for general purposes. For exposure to specific environments, check with
chemical compatibility charts before installing.
• The user is responsible for the selection of bolting and gasket materials which will
fall within the limits of the flange and its intended use, and which are suitable for
the service conditions.

Mounting location

Note: For complete mounting instructions for all probe versions, please
see the SITRANS LG200 instruction manual.
Recommendations
• Easy access for programming via device push buttons.
• An environment suitable to the enclosure rating and materials of construction.
Precautions
• Do not place insulating material around any part of SITRANS LG200 transmitter including
the probe flange as this may cause excessive heat buildup.
• Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to
variable frequency motor speed controllers.
• Avoid interference to the emission cone from obstructions or from the fill path.
Single Rod:
1. Do not mount in nozzles <50 mm (2") in
diameter.
2. Mount in applications where ratio of
diameter:length is 1:1 or greater. Any ratio less
than 1:1 (for example, a 2"x6" nozzle = 1:3) may
require a blocking distance and/or dielectric
adjustment.
3. Do not use pipe reducers.
4. Keep conductive objects away from probe to
ensure proper performance.
Twin rod:
1. Active rod must be mounted at least 25 mm
(1") away from any obstructions.
2. Minimum stillwell or nozzle diameter for
probe is 76 mm (3").
.
Page EN-4
SITRANS LG200 – QUICK START MANUAL
Correct:
dia.
Incorrect:
7ML19985XG81
length