Configuration - Parameters Menu
19 parameters are available, indicated by the letter "b", which are not modifiable from Remote Timer Control.
Table 4- Parameters - Configuration
Parameter
Description
b01
Gas type selection
b02
Boiler type selection
b03
System water pressure protection selection
b04
Fan max. frequency in DHW
b05
Fan max. frequency in heating
b06
Fan min. frequency in DHW/heating
b07
Fan min. Frequency Offset
b08
Variable output Relay operation selection
b09
Post-Ventilation
b10
Boiler room pre-ventilation
b11
Boiler room post-ventilation
b12
Fume sensor
b13
Not implemented
b14
Fumes Max Temperature
b15
Fan type selection
b16
Pump antiblock operation time
b17
High voltage input
b18
Password
b19
Module Activation
Notes
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is mo-
dified.
334
Range
Natural Gas/LPG
1 = Heating only
2 = Combi with storage tank with double pump
3 = Combi with storage tank with diverter valve
4 ÷ 9 = Not used
0 = Pressure switch
1 = Flow switch 1 sec
2 = Flow switch 3 sec
3 = Flow switch 5 sec
4 = Flow switch 10 sec
5 = Pressure transducer
0-255 Hz
0-255 Hz
0-255 Hz
0-255 Hz
0=Burner lit
1=Legionella pump
2=Boiler room ventilation
3=Motor-operated shutoff valve
0-120 seconds
1-15 minutes
1-15 minutes
OFF = Deactivated,
ON = Enabled
0 ÷ 90 °C
0-125°C
--
0-20 seconds
0 = Remote reset
1 = Disable all modules
2 = Not used
3 = Enable heating request
0 ÷ 999
ON-OFF
cod. 3541V120 - Rev 00 - 09/2021
MACH
Natural gas
1
0
210 Hz
210 Hz
60 Hz
40 Hz
0
30
1
1
OFF
45
110
--
5
0
418
ON
EN