Notice on installation
Warning
Connecting the wallbox to the power supply other than as specified in this section can result
in incompatibility of the installation as well as the risk of electric shock, and thus cause da-
mage to the wallbox, and injury or death.
› Only connect the wallbox to a power supply in a configuration that is specified in
this section.
Installation advice
Ground
Input
MCB
RCD
NOTE: For a TT or IT electric grid with 230
V from line to line, the charging station
must be installed with one phase being
connected to clamp L1 and the other
phase being connected to clamp N.
TN-system
TT-system
IT-system
1-phase
3-phase
C-characteristic (MCB must be selected to match the
amperage settings of the charging station, considering
MCB manufacturer specifications)
40 A, 30 mA, AC Type A
NOTE: Make sure that the provided ground
connection meets the local regulations.
The ground loss monitor functionality of
the wallbox is limited to physical ground
loss detection and cannot detect quality.
PE-cable
Earth electrode installed
separately (to be installed)
230 V ± 10 %, 50 Hz
400 V ± 10 %, 50 Hz
23