Ingersoll Rand TS1A-13A Manual De Manejo Y Mantenimiento página 21

Secador refrigerado
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

TS–6A 50/60Hz
KEY
A.
Electrical conduit connection
B.
Compressed air inlet
50Hz: 3" BSP female
380v / 3 / 50Hz: 3" BSP female
All other 60Hz: 3" NPT female
NOTES:
1.
Weight (approximate):
TS–6A: 429 kg (944 lb)
2.
Refrigerant: R–404A
Tolerance on dimensions: 13mm (0.5") unless otherwise
3.
stated.
4.
305mm (12") minimum electrical cable length allowance is
required between the electrical cable entry (A) and the mains
terminal block.
All manuals and user guides at all-guides.com
8.0 GENERAL INFORMATION
TS1A–13A
http://air.irco.com
C.
Compressed air discharge
50Hz: 3" BSP female
380v / 3 / 50Hz: 3" BSP female
All other 60Hz: 3" NPT female
D.
Condensate drain
50Hz: 1/4" BSP female
380v / 3 / 60Hz: 1/4" BSP female
All other 60Hz: 1/4" NPT female
5.
Recommended clearance on all sides 1m(3ft) front panel with
starter door may require more as defined by local and national
electrical codes.
6.
External piping shall not exert any unresolved moments or
forces on it.
7.
There should be no plastic piping, not approved by IR, attached
to this unit or used for any lines downstream.
8.
Field installed ducting to and from the dryer can not add more
than 1.0mm (0.04) water air resistance.
19
Tabla de contenido
loading

Tabla de contenido