Connections made with this tool (2879-20), Adapter (49-15-PUAD) and combination of die
and connector part numbers in the charts below produce cULus classified crimps according
to the UL 486A-B standard. *The connections made with these die cat. no.'s create cULus
classified crimps without the use of the adapter.
Anderson Blackburn
Splice
VHS,
Model #'s
VHSS
Lug
VHCL,
Model #'s
VHCS
Wire Size
Color
(Code only)
Code
#8 AWG
RED
#6 AWG
BLUE
#4 AWG
GRAY
#2 AWG
BROWN
#1 AWG
GREEN
1/0 AWG
PINK
2/0 AWG
BLACK
3/0 AWG
ORANGE
4/0 AWG
PURPLE
250 MCM
YELLOW
300 MCM
WHITE
350 MCM
RED
400 MCM
BLUE
500 MCM
BROWN
600 MCM
GREEN
750 MCM
BLACK
750 MCM
BLACK
800 MCM
ORANGE
1000 MCM
WHITE
Anderson
Splice
VACS
Model #'s
Lug
VACL
Model #'s
Wire Size
Color
(Code Only)
Code
#8 AWG
BLUE
#6 AWG
GRAY
#4 AWG
GREEN
#2 AWG
PINK
#1 AWG
GOLD
1/0 AWG
TAN
2/0 AWG
OLIVE
3/0 AWG
RUBY
4/0 AWG
WHITE
250 MCM
RED
300 MCM
BLUE
350 MCM
BROWN
400 MCM
GREEN
500 MCM
PINK
600 MCM
BLACK
750 MCM
YELLOW
750 MCM
YELLOW
800 MCM
GRAY
1000 MCM
BROWN
Number of crimps is a minimum. Additional crimps would not negatively affect the integrity of the connection so long as they are uniformly
placed between the intended crimp area of the connector, typically outlined with color bands or knurls. For the latest listing of approvals, visit
milwaukeetool.com. For technical or service assistance, contact Milwaukee Customer Service at 1-800-729-3878.
Copper Short & Long Barrel Lugs & Splices
Burndy
®
CSP,
YS, YS-L,
CU
YS-T
CTL,
YA, YAZ, YA-L, YA-2L,
CTL-2,
YA-2LN, YA-L-NT,
CTL-L,
YA-L-2NT, YA-L-TC,
LCN
YA-L-2TC, YA-2N,
YA-TC, YA-2TC
Die
Indentation
Cat. No.
Mark
49-12-U008C
8
49-12-U006C
6
49-12-U004C
4
49-12-U002C
2
49-12-U001C
1
49-12-U01AC
1/0
49-12-U02AC
2/0
49-12-U03AC
3/0
49-12-U04AC
4/0
49-12-U250C
250
49-12-U300C
300
49-12-U350C
350
49-12-U400C
400
49-12-U500C
500
49-12-U600C
600
49-12-U750C
750
49-15-P750C*
750P
49-15-P800C*
800P
49-15-P000C*
1000P
Dual Rated Lugs & Splices
Blackburn
Burndy
®
ASP
YS-A
ATL
YA-A,
YA-ATN
Die
Indentation
Cat. No.
Mark
49-12-U008
8
49-12-U006
6
49-12-U004
4
49-12-U002
2
49-12-U001
1
49-12-U01A
1/0
49-12-U02A
2/0
49-12-U03A
3/0
49-12-U04A
4/0
49-12-U250
250
49-12-U300
300
49-12-U350
350
49-12-U400
400
49-12-U500
500
49-12-U600
600
49-12-U750
750
49-15-P750*
750P
49-15-P800*
800P
49-15-P000*
1000P
TABLE A
ILSCO
CT, CTL
CLN, CLND, CLNS,
CLW, CLWD, CRA,
CRB, CRA-L, CRB-L,
CRA-2L, CRB-2L,
CSW, CSWS
Splices: # of Crimps per Side
®
Anderson
Blackburn
1
1
2
Lugs: 2
Splices: N/A
2
2
3
3
ILSCO
AS,
ASN
ACL, ACN, ALND, ALNS,
2ACL, 2ACN, ALNN
Splices: # of Crimps per Side
®
Anderson
Blackburn
Lugs: N/A
Lugs: 1
Splices: 1
Splices: N/A
1
1
2
2
3
3
4
Panduit
Penn-Union
SCH, SCL,
BBCU,
SCS, SCSS
BCU
LCA, LCAS,
BBLU,
LCB, LCC,
BLU
LCD
Lugs: Total # of Crimps
Burndy
ILSCO Panduit
1
1
1
2
2
2
3
3
3
Panduit
Penn-Union
SA
BCUA
LAA,
BLUA
LAB
Lugs: Total # of Crimps
Burndy
ILSCO
Panduit
1
1
2
2
2
3
3
3
4
4
4
T&B
54504-54528,
54804-54828
54104-54128,
54204-54228,
54930BE-54928BE,
54850BE-54882BE
Penn-Union
T&B
1
1
2
2
3
3
T&B
60501-60584
60101-60184 &
60230-60284
Penn-Union T&B
Lugs: 1
Splices: N/A
1
1
2
2
3
3
4