Piping Length & Elevation
If the pipe is too long, both the capacity and reliability of
the unit will drop. As the number of bends increases,
resistance to the flow of refrigerant system increases, thus
lowering cooling capacity. As a result, the compressor may
become defective. Always choose the shortest path and
follow the recommendations as tabulated below:
Indoor Unit
Outdoor Unit
Model
07
Maximum length, m (ft), L
12 (39) 12 (39) 12 (39) 15 (49) 15 (49)
Max. elevation, m (ft), H
5 (16.4) 5 (16.4) 5 (16.4) 8 (26.2) 8 (26.2)
Max. number of bends
10
Liquid pipe size
1/4"
Gas pipe size
3/8"
Remark: The refrigerant pre-charged in the outdoor unit
is for piping length up to 7.62 m/25 ft.
Piping Works
Do not use contaminated or damaged copper tubing. Do
not remove plastic, rubber plugs and brass nuts from the
valves, fittings, tubings and coils until you are ready to
connect suction or liquid line into valves or fittings.
If any brazing work is required, ensure that the nitrogen
gas is passed through coil and joints while the brazing
work is being done. This will eliminate soot formation on
the inside walls of the copper tubings.
Cut the connection pipe with a pipe cutter.
Remove burrs from cut edges of the pipes with remover.
Hold the end of the pipe downwards to prevent metal chips
from entering the pipe.
Insert the flare nuts, mounted on the connection parts of
both the indoor unit and outdoor unit onto the copper pipes.
Flare the pipe with extra length above the flaring tool as
shown in the table.
The flared edge must be even and not cracked or scratched.

REFRIGERANT PIPING

L
H
10
15
20
25
10
10
10
10
1/4"
1/4"
1/4"
3/8"
3/8"
1/2"
5/8"
5/8"
Cutting Copper Tube
1/4t
Remove Burr
Copper Tube
Swaging Block
Ø Tube, D
Inch
mm
1/4"
6.35
3/8"
9.52
1/2"
12.70
5/8"
15.88
3/4"
19.05
Piping Connection To The Units
Align the center of the piping and tighten the flare nut
sufficiently with fingers.
Finally, tighten the flare nut with the torque wrench until
the wrench clicks.
Flare Joint
Indoor Piping
Spanar
Pipe Size mm / (in)
6.35 (1/4)
9.53 (3/8)
12.7 (1/2)
15.88 (5/8)
19.05 (3/4)
1-5
A (mm)
Imperial
Rigid
1.3
0.7
1.6
1.0
1.9
1.3
2.2
1.7
2.5
2.0
Flared Tube
Flare Nut
Torque Wrench
Torque Nm / (ft - lb)
18(13.3)
42(31.0)
55(40.6)
65(48.0)
78(57.6)