18-19. SLOW-DOWN RAMP drAO and drAC (0 – 20 x 100ms) default = 6
This parameter allows you to set the duration of the slowdown ramp (time to get from Spn to SPL). With drAO you can change the
ramp that takes place in the opening, while with DraC you can change the ramp that takes place in the closing of the automation.
The higher the value, the longer the ramp. With dra = 0, ramps are deactivated and the motor changes abruptly from full speed
to slow-down speed.
20. DEVICES FUNCTIONALITY TEST tPh (0 – 7) default = 0
It gives you the option to choose which devices to test on. Enabling the test function is carried out the functional verification of the
same before each movement that starts with stationary automation. WARNING! It is not performed in the case of fast reversals.
•
Value 0 = No device to test.
•
Value 1 = Test on PH1.
•
Value 2 = Test on PH2.
•
Value 3 = Test on PH1 and PH2.
•
Value 4 = Test on PH3.
•
Value 5 = Test on PH3 and PH1.
•
Value 6 = Test on PH3 and PH2.
•
Value 7 = Test on PH3, PH2 and PH1.
21. CONFIGURATION OF THE FLASHING OUTPUT FPr (0 – 1) default = 1
Two modes are selectable for the flashing output:
•
Value 0 = The output remains fixed. You will need to use a flashing light device with auto flashing circuit (B.RO LIGHT 24 Vac).
•
Value 1 = Flashing output. You will need to use a flashing light device without auto flashing circuit (B.RO LIGHT FIX 24 Vac).
22. TIME OF FLASHING BEFORE MOVEMENT TPr (0 – 10 seconds) default = 0
Flashing of the light before every movement, whose duration is defined by the parameter tpr.
23. DEAD-MAN MODE dEA (0 – 1) default = 0
In DEAD-MAN mode, the automation moves exclusively until the control is present; at the release, the automation stops.
The enabled commands are OPEN and CLOSE. The SS command is inactive. All automatic operations, including short or total
reversals, are disabled. All security is disabled except the STOP.
24. CYCLE THRESHOLD FOR ASSISTANCE REQUEST Ser (0 – 100 x 1000 cicles) default = 0
You can set from the menu the number of cycles expected before the control unit requires assistance. The request is signalled by
replacing the normal functional flashing with a fast flashing during handling (only if fpr = 1).
25. CONTINUOUS FLASHING FOR ASSITANCE REQUEST SEF (0 – 1) default = 1
Enabling the function requires the flashing light to continue flashing with automation closed as a service request.
26. DURATION OF THE MOTOR STOP RAMP SFt (0 – 20 x 100 ms) default = 3
Duration of the ramp to switch from a state of movement to the complete stop of the automation, in case an immediate stop
is required (alarm or protection events). WARNING! - this parameter is not considered in case of STOP intervention by wired
command.
27. TIME OF ENCODER EnP (4 – 80 ms) default = 7
Encoder output pulse length at motor speed.
28. SETTING THE DEFAULT VALUE (RESET) dEF
By accessing the def entry you can restore the factory configuration of the plant. The reset affects all the parameters of the base
menu and the advanced menu while it does not affect the width of the learned movement of the boom.
To reset access the def item, then confirm with the extended press of the "MENU" button. Hold down the "MENU" button until the
number 0 flashes, release the button. Press and hold the "MENU" key. It starts a countdown "d80, d79, ... , d01" and when it is
finished the reset is executed and the word done is displayed.
29. DISPLAY SINGLE TRANSMITTER MEMORY POSITION TRS
By accessing the Trs entry you can view the memory location where a transmitter has been stored. To perform the function access
the item, then confirm with the extended press of the "MENU" button.
Hold down until the SEE print display, release the button.