FAS 3000 FLOW CHART
GROUP TIMER
The FAS3000 is equipped with a group timer that is enabled and started by applying +24VDC to the Group Timer Start
input. The group timer is stopped by a GROUP ACCEPT. If the group timer is allowed to expire, the OK LED will flash on
and off, and the error code ER06 will be displayed until the GROUP is complete or the GROUP RESET is activated. The
Group Timer Start input must be maintained in order for the timer to run. Also, the group timer must be disabled and
enabled in order to restart the timer. The maximum group time is 99.9 seconds.
When the cycle timer expires, this message will appear on the
display until the GROUP is complete or a GROUP RESET is
activation.
Use these buttons on the keypad to
increment or deincrement the flashing digit.
Use these buttons to edit the next digit.
Press this key to save the change and exit
the menu option.
Press this key to exit the menu option
without making the change.