Set the delay time at zero (parameter AUX3 IN DELAY in the DIGITAL IN/OUT MENU) of the minimum
pressure switch alarm. With the system under pressure, inhibit pump operation with the bypass jumpers
on the board (see chapter 4.2).
Configure the set to work in automatic mode. Slowly open a drawing point to bring down the pressure
in the delivery manifold. As the pressure lowers, the pump leds will light; the pumps will not start
because operation has been inhibited. When the established pressure value (minimum pressure) is
reached, turn the regulating screw on the minimum pressure switch to modify the threshold of
intervention (turn clockwise to increase the threshold, counter clockwise to decrease it). The lighting of
the red fault led and the respective alarm on the display indicate intervention of the protection device.
On completing adjustment, reset the CONV.L.SWITCH alarm delay (recommended 20 seconds) in the
parameter AUX3 IN DELAY in the DIGITAL IN/OUT MENU.
6.2.9 NIGHT/DAY FUNCTION
Phase
Display
0 NIGHT/DAY
1
NIGHT/DAY FUNC.
2
NIGHT/DAY VALUE
3
N/D START HOUR
4
N/D START MIN.
5
N/D END HOUR
6
N/D END MIN.
6.2.10 PROGRAMMING ANALOG INPUTS / OUTPUTS
Phase
Display
0 ANALOG. IN/OUT
1
AI1 SENSOR TYPE
2
ZERO ADJUST AI1
Comment
Only for systems with a sensor
Threshold change enable in N mode (night-
time).
May be disabled by the internal clock, by an
external control connected to AUX3, or by
the Internal Clock or External control.
Decrease value of the pressure SET when
working in N (night) mode. When night-time
operation is enabled, all the thresholds are
decreased by the value set in this parameter.
The letter N is highlighted at top right of the
display.
Setting of the hour for activating the N/D
change.
Setting of the minutes for activating the N/D
change.
Setting of the hour for deactivating the N/D
change.
Setting of the minutes for deactivating the
N/D change.
Comment
Only for systems with a sensor
Type of transducer connected to the
analog input AI1 (if selected on System)
Visible only if 4-20mA selected.
Acquisition of input zero 4 4-20 mA
Adjustment is possible only in the range
3.5... 4.5mA
If adjustment has a positive result the
message SENSOR ADJUST OK appears
If out of range the message SENSOR
ADJUST KO appears
Field
DISABLED
DISABLED
INTERNAL
CLOCK
EXT.ON
/OFF
INT.EXT
-FS..0..FS
-1.00 bar
Field
Default
4-20 mA
4-20 mA
0-20 mA
0-10 V
0-2 V
YES
NO
NO
en
Default
47