Duct Smoke Detector
If in doubt, use an airflow measuring device to measure the air
speed in the duct.
3.2
Installation position
Avoid selecting an installation position near ducts with dead-air
space or areas with turbulence.
Turbulence mainly occurs near connecting flanges, branches,
tight bends, and long, straight ducts.
Place the FAD-420-HS-EN at a distance of at least three times
the width of the ventilation duct [b ≥ 3 x d] away from these
critical areas (see Figure 3.1).
3.3
Housing position
The FAD-420-HS-EN must only be mounted in a vertical or
horizontal position (see Figure 3.2).
1
Figure 3.2 Position of housing on the ventilation duct
No.
e
Bosch Sicherheitssysteme GmbH
2
Description
Airflow direction
Installation guide
Installation/configuration notes | en
F.01U.033.733 | 5.0 | 2011.11
3
57