Control Circuit Wiring Diagram; Wiring Diagram - WEG ABWC Serie Instrucciones De Instalación, Operación Y Mantenimiento

Tabla de contenido

15 CONTROL CIRCUIT WIRING DIAGRAM

15.1 WIRING DIAGRAM

This diagram considers the circuit breaker in the inserted position, in the open position (OFF) and motor loaded.
In the withdrawable version (with truck), the truck release latch must be in the regular (released) position.
www.weg.net
Auxiliary position contacts, optional item for
the withdrawable circuit-breaker:
311
~
344
Cell switch
Accessory code description:
Axc
Auxiliary switch
L
Long time delay trip indicator
SI
Short time delay/instantaneous
G
Ground fault trip indicator
CL1~CL4
Cell switch
M
Motor
Closing coil
CC
Shunt tripping device 1
SHT1
SHT2
Shunt tripping device 2
UVT coil
UVT
Z1
Z2
ZSI input
Z3
Z4
ZSI output
E1
E2
External CT
VN
~
V3
Voltage module
485+
~
485-
RS485 Communication
311
~
314
Auxiliary position switch
Terminal code description:
11
12
~
41
42
Auxiliary switch "b" contact
11
14
~
41
44
Auxiliary switch "a" contact
U3
U2
Spring loaded
U1
U2
Motor of spring charging
A1
A2
Closing coil
C1
C2
Shunt trip
C11 C12
2
nd
shunt trip
D1
D2
Voltage input terminal of UVT
81
82
Alarm trip 1
181 182
Alarm trip 2
Ready to close, the circuit breaker is
251 252
turned off and the spring is loaded
R1
R2
Control power
513
~
544
Alarm contact
R11 R22
Alarm reset
ABWC Compact Air Circuit Breaker | 57
Tabla de contenido
loading