WEG ABWC Serie Instrucciones De Instalación, Operación Y Mantenimiento página 48

Tabla de contenido
www.weg.net
Relay setting
display
Display
Address
Communication
Speed
View
Time
Setting
48 | ABWC Compact Air Circuit Breaker
Measurement display
Commun.
Commun.
addr. setting
speed setting
Key
1. Pressing the MENU key twice from the measurement display leads to the
M
communication address setting screen.
2
2. The communication address can be selected from 1 to 247.
3. Briefly pressing the up key increases the Address by 1.
4. Briefly pressing the up key increases the Address by 10.
1. Press the Enter key to save the setting or press ESC/RESET to return to the
measurement display.
2. If saved successfully, "SAVE" is displayed on the screen, and the
measurement display is shown; pressing the ESC/RESET key moves to the
measurement display without saving.
1. Pressing the MENU key three times from the measurement display leads to
the communication speed setting screen.
M
3
2. The communication speed can be set through the baud rates
38400/19200/9600.
3. Pressing the up/down keys will display the baud rate value.
1. Press the Enter key to save the setting or press ESC/RESET to return to the
measurement display.
2. If saved successfully, "SAVE" is displayed on the screen, and the
measurement display is shown; pressing the ESC/RESET key moves to the
measurement display without saving.
1. Pressing the MENU key four times from the Measurement display leads to
the current time display.
M
2. The current time is displayed with "hour" and "minute" in the 24 hour format
4
and the dot between the hour and minute flashes every second.
3. Unless the current time is set, it will be set to "1 hour and 1 minute", because
the start time is defined as "1 hour 1 minute 1 second 1 of January 2000".
1. Pressing the Enter key once from the time display leads to the time setting.
▼▼
➋ Change it using the up/down keys in the year setting mode and then press
Enter to switch to the month setting mode. (The user can select between 2000
and 2099.)
➌ Change it using the up/down keys in the month setting mode and then press
Enter to switch to the day setting mode. (The user can select between 1 and 12.)
▼▼
➎ Change it using the up/down keys in the day setting mode and then press
Enter to switch to the hour setting mode. (The user can select between 1
3
and 31.) There is no leap year/month.)
➏ Change it using the up/down keys in the hour setting mode and then press
Enter to switch to the minute setting mode. (The user can select between 0
and 23.)
▼▼
➑ Change it using the up/down keys in the minute setting mode and then press
Enter to switch to the second setting mode. (The user can change minutes
and seconds between 0 and 59)
5
➒ If the user presses the Enter key in seconds mode, the time is saved in the
RTC and SAVE will be displayed for one second before returning to the home
screen.
➓ If the user presses the reset key, the time will not be saved, and the display
will return to the home screen.
Table 12.3:
Current
Event list
time display
Content
: It is on the left and year/month will be displayed (February/2013)
: It is in the center and the day/time will be displayed. (18/11 hours)
: It is on the right and the minute/second will be displayed. (5 minutes 11
seconds)
Firmware
version
Tabla de contenido
loading

Tabla de contenido