Relay setting
display
Display
Event
Firmware
version
50 | ABWC Compact Air Circuit Breaker
Measurement display
Commun.
Commun.
addr. setting
speed setting
Key
1. Pressing the MENU key five times from the Measurement display leads to the Event
List.
M
2. The Event List displays fault event information. The screen shows up to ten events and
5
each piece of information displays the fault current, fault type, fault phases and time of
occurrence, including second, minute, hour, date, month and year.
1. "Ii=": Fault: long time/short time/instantaneous/ground fault
2. "1600A": Fault current
3. "
": Fault phase: R, S, T, N
4. ACB OCRN/type A can save 10 events and the Event List indicates the order of
occurrence.
5. When displaying the last event, only one segment will be displayed in the Event
List. Pressing the up key will increment the segment and the previously saved
event will be displayed.
1. If there is no date in the Event List, the expression "Empty" will be displayed.
1. Pressing "Enter" in the Event List displays the time information of the
corresponding events
: View of the 7th Event (Event List)
▼▼
: View of the Event Year/Month
➌ Pressing Enter once will display Year/Month information. The screen on the left
indicates "January 2007"
1. Pressing Enter twice will display Date/Hour information.
➍: The current screen indicates "08th, 1 hour"
2
➎: View of the Event Date/Time
➏: Event List: View of the 7th Event
1. Pressing Enter three times will display minute/second information.
➐: The current screen indicates "12 minutes 51 seconds".
3
➑: View of the Event Minutes/Seconds
➒: Event List: View of the 7th Event
M
1. Pressing the MENU key six times from the Measurement display leads to the
6
Firmware Version.
Table 12.5:
Current
Event list
time display
Content
Firmware
version