10. Detailed settings
10.4 Setting the signal limits
The signal limits define the current range within which the output signal can be. Above or
below the signal limits are the preset limits for the output signal.
Setting range: 3.8 ... 20.5 mA or 4.0 ... 20.0 mA
(NAMUR recommendation NE43 for process instruments is 3.8 ... 20.5 mA)
1. Open the operating menu with [↵].
Select "Detail setup" and confirm with [↵].
2. Select "Current out" and confirm with [↵].
3. Select "Limits" and confirm with [↵].
4. Select signal limits and confirm with [↵].
» Signal limits are set.
10.5 Setting the contrast of the LC display
Setting range: 1 ... 9 (in steps of 1)
1. Open the operating menu with [↵].
Select "Detail setup" and confirm with [↵].
2. Select "Contrast" and confirm with [↵].
3. Change figure using [▲] [▼] and confirm with [↵].
» Contrast is set.
10.6 Restoring factory setting
1. Open the operating menu with [↵].
Select "Detail setup" and confirm with [↵].
2. Select "Reset" and confirm with [↵].
WIKA operating instructions, model DMSU21A
EN
47